range of product |
Altistart 48
|
|
---|---|---|
product or component type |
Soft starter
|
|
product destination |
Asynchronous motors
|
|
product specific application |
Heavy duty industry and pumps
|
|
device short name |
ATS48
|
|
power supply voltage |
230…415 V – 15…10 %
|
|
motor power kW |
55 kW at 400 V connection to the motor delta terminals for standard applications
55 kW at 400 V connection to the motor delta terminals for severe applications 15 kW at 230 V connection in the motor supply line for severe applications 18.5 kW at 230 V connection in the motor supply line for standard applications 30 kW at 230 V connection to the motor delta terminals for severe applications 30 kW at 400 V connection in the motor supply line for severe applications 37 kW at 230 V connection to the motor delta terminals for standard applications 37 kW at 400 V connection in the motor supply line for standard applications |
|
power dissipation in W |
201 W for severe applications
245 W for standard applications |
|
utilisation category |
AC-53A
|
|
type of start |
Start with torque control (current limited to 5 In)
|
|
Icl nominal current |
75 A for connection in the motor supply line for severe applications
75 A for connection in the motor supply line for standard applications 130 A for connection to the motor delta terminals for severe applications 130 A for connection to the motor delta terminals for standard applications |
|
IP degree of protection |
IP20
|
assembly style |
With heat sink
|
|
---|---|---|
function available |
External bypass (optional)
|
|
power supply voltage limits |
195…456 V
|
|
power supply frequency |
50…60 Hz – 5…5 %
|
|
power supply frequency limits |
47.5…63 Hz
|
|
device connection |
To the motor delta terminals
In the motor supply line |
|
factory setting current |
69 A
|
|
[Uc] control circuit voltage |
220 – 15 % to 415 + 10 %, 50/60 Hz
|
|
control circuit consumption |
30 W
|
|
discrete output number |
2
|
|
discrete output type |
(LO1) logic output 0 V common configurable
(LO2) logic output 0 V common configurable (R1) relay outputs fault relay NO (R2) relay outputs end of starting relay NO (R3) relay outputs motor powered NO |
|
output absolute accuracy precision |
+/- 5 %
|
|
minimum switching current |
10 mA at 6 V DC for relay outputs
|
|
maximum switching current |
Logic output 0.2 A at 30 V DC
Relay outputs 1.8 A at 230 V AC inductive load, cos phi = 0.5 20 ms Relay outputs 1.8 A at 30 V DC inductive load, cos phi = 0.5 20 ms |
|
discrete input number |
5
|
|
discrete input type |
PTC, 750 Ohm at 25 °C
(Stop, Run, LI3, LI4) logic, <= 8 mA 4300 Ohm |
|
discrete input voltage |
24 V <= 30 V
|
|
discrete input logic |
Positive logic Stop, Run, LI3, LI4 at State 0: < 5 V and <= 2 mA at State 1: > 11 V, >= 5 mA
|
|
starting current |
0.4…1.3 Icl adjustable
|
|
analogue output type |
Current output AO: 0-20 mA or 4-20 mA, impedance <500 Ohm
|
|
communication port protocol |
Modbus
|
|
connector type |
1 RJ45
|
|
communication data link |
Serial
|
|
physical interface |
RS485 multidrop
|
|
transmission rate |
4800, 9600 or 19200 bps
|
|
max nodes number |
31
|
|
protection type |
Phase failure: line
Thermal protection: motor Thermal protection: starter |
|
marking |
CE
|
|
type of cooling |
Forced convection
|
|
operating position |
Vertical +/- 10 degree
|
|
height |
290 mm
|
|
width |
190 mm
|
|
depth |
235 mm
|
|
net weight |
8.3 kg
|
|
Motor power range AC-3 |
15…25 kW at 200…240 V 3 phases
30…50 kW at 200…240 V 3 phases 30…50 kW at 380…440 V 3 phases 55…100 kW at 380…440 V 3 phases |
|
motor starter type |
Soft starter
|
Reviews