range of product |
Altistart 48
|
|
---|---|---|
product or component type |
Soft starter
|
|
product destination |
Asynchronous motors
|
|
product specific application |
Heavy duty industry and pumps
|
|
device short name |
ATS48
|
|
power supply voltage |
208…690 V – 15…10 %
|
|
motor power kW |
220 kW 230 V for standard applications
355 kW 400 V for severe applications 400 kW 400 V for standard applications 400 kW 440 V for severe applications 500 kW 440 V for standard applications 500 kW 500 V for standard applications 500 kW 525 V for standard applications 630 kW 660 V for severe applications 630 kW 690 V for severe applications 710 kW 660 V for standard applications 710 kW 690 V for standard applications |
|
Maximum Horse Power Rating |
200 hp 208 V for severe applications
250 hp 208 V for standard applications 250 hp 230 V for severe applications 300 hp 230 V for standard applications 500 hp 460 V for severe applications 600 hp 460 V for standard applications 600 hp 575 V for severe applications 800 hp 575 V for standard applications |
|
power dissipation in W |
2073 W for standard applications
2537 W for standard applications |
|
utilisation category |
AC-53A
|
|
type of start |
Start with torque control (current limited to 5 In)
|
|
Icl nominal current |
790 A connection in the motor supply line for standard applications
790 A connection in the motor supply line for severe applications |
|
IP degree of protection |
IP00
|
assembly style |
With heat sink
|
|
---|---|---|
function available |
External bypass (optional)
|
|
power supply voltage limits |
177…759 V
|
|
power supply frequency |
50…60 Hz – 5…5 %
|
|
power supply frequency limits |
47.5…63 Hz
|
|
device connection |
In the motor supply line
|
|
factory setting current |
720 A
|
|
[Uc] control circuit voltage |
110 – 15 % to 230 + 10 %, 50/60 Hz
|
|
control circuit consumption |
80 W
|
|
discrete output number |
2
|
|
discrete output type |
LO1) logic output 0 V common configurable
LO2) logic output 0 V common configurable R1) relay outputs fault relay NO R2) relay outputs end of starting relay NO R3) relay outputs motor powered NO |
|
output absolute accuracy precision |
+/- 5 %
|
|
minimum switching current |
10 mA 6 V DC relay outputs
|
|
maximum switching current |
Logic output 0.2 A 30 V DC
Relay outputs 1.8 A 230 V AC inductive, cos phi = 0.5 20 ms Relay outputs 1.8 A 30 V DC inductive, cos phi = 0.5 20 ms |
|
discrete input number |
5
|
|
discrete input type |
PTC, 750 Ohm 77 °F (25 °C)
Stop, Run, LI3, LI4) logic, <= 8 mA 4300 Ohm |
|
discrete input voltage |
24 V <= 30 V
|
|
discrete input logic |
Positive logic Stop, Run, LI3, LI4 < 5 V <= 2 mA > 11 V, >= 5 mA
|
|
starting current |
0.4…1.3 Icl adjustable
|
|
analogue output type |
Current output AO 0-20 mA or 4-20 mA 500 Ohm
|
|
communication port protocol |
Modbus
|
|
connector type |
1 RJ45
|
|
communication data link |
Serial
|
|
physical interface |
RS485 multidrop
|
|
transmission rate |
4800, 9600 or 19200 bps
|
|
max nodes number |
31
|
|
protection type |
Phase failure line
Thermal protection motor Thermal protection starter |
|
marking |
CE
|
|
type of cooling |
Forced convection
|
|
operating position |
Vertical +/- 10 degree
|
|
height |
35.04 in (890 mm)
|
|
width |
30.31 in (770 mm)
|
|
depth |
12.40 in (315 mm)
|
|
Net Weight |
253.53 lb(US) (115 kg)
|
|
Motor power range AC-3 |
110…220 kW 200…240 V 3 phase
250…500 kW at 380…440 V 3 phases 250…500 kW 480…500 V 3 phase |
|
motor starter type |
Soft starter
|
Reviews