range of product |
TeSys D
|
|
---|---|---|
range |
TeSys
|
|
product or component type |
Contactor
|
|
device short name |
LC1D
|
|
contactor application |
Resistive load
Motor control |
|
utilisation category |
AC-2
AC-3 AC-1 AC-4 |
|
control circuit type |
DC standard
|
|
poles description |
3P
|
|
pole contact composition |
3 NO
|
|
[Ie] rated operational current |
40 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit |
|
motor power kW |
18.5 kW at 380…400 V AC 50 Hz (AC-3)
22 kW at 500 V AC 50 Hz (AC-3) 30 kW at 660…690 V AC 50 Hz (AC-3) 22 kW at 1000 V AC 50 Hz (AC-3) 22 kW at 415 V AC 50 Hz (AC-3) 22 kW at 440 V AC 50 Hz (AC-3) 11 kW at 220…230 V AC 50 Hz (AC-3) 9 kW at 400 V AC 50 Hz (AC-4) |
coil technology |
Built-in bidirectional peak limiting diode suppressor
|
|
---|---|---|
Front cover |
With
|
|
motor power hp |
3 hp at 115 V AC 60 Hz for 1 phase motors
5 hp at 230/240 V AC 60 Hz for 1 phase motors 10 hp at 200/208 V AC 60 Hz for 3 phases motors 10 hp at 230/240 V AC 60 Hz for 3 phases motors 30 hp at 460/480 V AC 60 Hz for 3 phases motors 30 hp at 575/600 V AC 60 Hz for 3 phases motors |
|
auxiliary contacts type |
type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
type mirror contact 1 NC conforming to IEC 60947-4-1 |
|
auxiliary contact composition |
1 NO + 1 NC
|
|
[Uc] control circuit voltage |
24 V DC
|
|
time constant |
34 ms
|
|
[Ui] rated insulation voltage |
Control circuit: 600 V CSA certified
Control circuit: 600 V UL certified Power circuit: 600 V CSA certified Power circuit: 600 V UL certified Control circuit: 690 V conforming to IEC 60947-1 Power circuit: 690 V conforming to IEC 60947-1 Power circuit: 1000 V conforming to IEC 60947-4-1 |
|
[Uimp] rated impulse withstand voltage |
8 kV conforming to IEC 60947
|
|
overvoltage category |
III
|
|
mounting support |
Rail
Plate |
|
flame retardance |
V1 conforming to UL 94
|
|
connections – terminals |
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²rigid
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²rigid Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1…2.5 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end Power circuit: screw terminals 1 cable(s) 2.5…25 mm²rigid Power circuit: screw terminals 2 cable(s) 2.5…16 mm²rigid Power circuit: screw terminals 1 cable(s) 2.5…25 mm²flexible without cable end Power circuit: screw terminals 2 cable(s) 2.5…16 mm²flexible without cable end Power circuit: screw terminals 1 cable(s) 2.5…25 mm²flexible with cable end Power circuit: screw terminals 2 cable(s) 2.5…10 mm²flexible with cable end |
|
tightening torque |
Control circuit: 1.2 N.m – on screw clamp terminal – with screwdriver flat Ø 6 mm
Control circuit: 1.2 N.m – on screw clamp terminal – with screwdriver Philips No 2 Power circuit: 5 N.m – on screw terminal – with screwdriver flat Ø 6 to Ø 8 mm |
|
[Ue] rated operational voltage |
Power circuit: <= 690 V AC 25…400 Hz
|
|
[Ith] conventional free air thermal current |
10 A (at 60 °C) for control circuit
60 A (at 60 °C) for power circuit |
|
Irms rated making capacity |
250 A DC for control circuit conforming to IEC 60947-5-1
800 A at 440 V for power circuit conforming to IEC 60947 |
|
rated breaking capacity |
800 A at 440 V for power circuit conforming to IEC 60947
|
|
associated fuse rating |
10 A gG for control circuit conforming to IEC 60947-5-1
80 A gG at <= 690 V coordination type 1 for power circuit 80 A gG at <= 690 V coordination type 2 for power circuit |
|
power dissipation per pole |
5.4 W AC-1
2.4 W AC-3 |
|
inrush power in W |
19 W (at 20 °C)
|
|
hold-in power consumption in W |
7.4 W at 20 °C
|
|
operating time |
20 ms opening
50 ms closing |
|
safety reliability level |
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
|
mechanical durability |
10000000 cycles
|
|
maximum operating rate |
3600 cyc/h 60 °C
|
|
minimum switching current |
5 mA for control circuit
|
|
minimum switching voltage |
17 V for control circuit
|
|
non-overlap time |
1.5 ms on de-energisation between NC and NO contacts
1.5 ms on energisation between NC and NO contacts |
|
insulation resistance |
> 10 MOhm for control circuit
|
|
rated operational power in W |
14 W at 24 V DC-13 – electrical durability: 10000000 cycles – for control circuit
48 W at 24 V DC-13 – electrical durability: 3000000 cycles – for control circuit 96 W at 24 V DC-13 – electrical durability: 1000000 cycles – for control circuit |
|
height |
127 mm
|
|
width |
85 mm
|
|
depth |
176 mm
|
|
net weight |
2.185 kg
|
|
compatibility code |
LC1D
|
Reviews
There are no reviews yet.