range |
TeSys
|
|
---|---|---|
product name |
TeSys F
|
|
product or component type |
Contactor
|
|
device short name |
LC1F
|
|
contactor application |
Resistive load
Motor control |
|
utilisation category |
AC-3
AC-1 AC-4 |
|
poles description |
3P
|
|
power pole contact composition |
3 NO
|
|
[Ue] rated operational voltage |
<= 1000 V AC 50/60 Hz
<= 460 V DC |
|
[Ie] rated operational current |
1000 A (at <40 °C) at <= 440 V AC AC-1
630 A (at <55 °C) at <= 440 V AC AC-3 |
|
motor power kW |
335 kW at 380…400 V AC 50/60 Hz (AC-3)
375 kW at 415 V AC 50/60 Hz (AC-3) 400 kW at 440 V AC 50/60 Hz (AC-3) 400 kW at 500 V AC 50/60 Hz (AC-3) 450 kW at 660…690 V AC 50/60 Hz (AC-3) 450 kW at 1000 V AC 50/60 Hz (AC-3) 200 kW at 220…230 V AC 50/60 Hz (AC-3) 100 kW at 400 V AC 50/60 Hz (AC-4) |
|
[Uc] control circuit voltage |
220 V AC 40…400 Hz
|
[Uimp] rated impulse withstand voltage |
8 kV
|
|
---|---|---|
overvoltage category |
III
|
|
[Ith] conventional free air thermal current |
1000 A (at 40 °C)
1250 A |
|
rated breaking capacity |
5040 A conforming to IEC 60947-4-1
|
|
[Icw] rated short-time withstand current |
5050 A 40 °C – 10 s
4400 A 40 °C – 30 s 3400 A 40 °C – 1 min 2200 A 40 °C – 3 min 1600 A 40 °C – 10 min |
|
associated fuse rating |
1000 A gG at <= 440 V
630 A aM at <= 440 V |
|
average impedance |
0.12 mOhm – Ith 1000 A 50 Hz
|
|
[Ui] rated insulation voltage |
1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 group C |
|
power dissipation per pole |
120 W AC-1
48 W AC-3 |
|
mounting support |
Plate
|
|
standards |
EN 60947-1
IEC 60947-4-1 JIS C8201-4-1 IEC 60947-1 EN 60947-4-1 |
|
product certifications |
LROS (Lloyds register of shipping)
CB UL RMRoS CSA ABS BV DNV RINA |
|
connections – terminals |
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end Power circuit: bar 2 cable(s) – busbar cross section: 60 x 5 mm Power circuit: bolted connection |
|
tightening torque |
Control circuit: 1.2 N.m
Power circuit: 58 N.m |
|
control circuit voltage limits |
Operational: 0.85…1.1 Uc 40…400 Hz (at 55 °C)
Drop-out: 0.25…0.5 Uc 40…400 Hz (at 55 °C) |
|
inrush power in VA |
1650 VA 40…400 Hz cos phi 0.9 (at 20 °C)
|
|
hold-in power consumption in VA |
22 VA 40…400 Hz cos phi 0.9 (at 20 °C)
|
|
heat dissipation |
20 W
|
|
operating time |
40…80 ms closing
100…200 ms opening |
|
mechanical durability |
5 Mcycles
|
|
maximum operating rate |
1200 cyc/h 55 °C
|
|
compatibility code |
LC1F
|
|
motor power range |
250…500 kW at 380…440 V 3 phases
110…220 kW at 200…240 V 3 phases 250…500 kW at 480…500 V 3 phases |
|
motor starter type |
Direct on-line contactor
|
|
contactor coil voltage |
220 V AC standard
|