range |
PowerLogic
|
|
---|---|---|
product name |
PowerLogic PM5000
|
|
device short name |
PM5310
|
|
product or component type |
Power meter
|
power quality analysis |
up to the 31st harmonic
|
|
---|---|---|
device application |
Multi-tariff
Power monitoring |
|
type of measurement |
Current
Voltage Frequency Power factor Energy Active and reactive power |
|
supply voltage |
100…415 V AC 45…65 Hz
125…250 V DC |
|
network frequency |
50 Hz
60 Hz |
|
[In] rated current |
1 A
5 A |
|
type of network |
1P + N
3P 3P + N |
|
maximum power consumption in VA |
10 VA at 415 V
|
|
ride-through time |
80 ms 120 V AC typical
100 ms 230 V AC typical 100 ms 415 V AC typical |
|
display type |
Backlit LCD
|
|
display resolution |
128 x 128 pixels
|
|
sampling rate |
64 samples/cycle
|
|
measurement current |
10…9000 mA
|
|
analogue input type |
Voltage (impedance 5 MOhm)
Current (impedance 0.3 MOhm) |
|
measurement voltage |
35…690 V AC 45…65 Hz between phases
20…400 V AC 45…65 Hz between phase and neutral |
|
frequency measurement range |
45…65 Hz
|
|
number of inputs |
2 digital
|
|
measurement accuracy |
Active energy +/- 0.5 %
Reactive energy +/- 2 % Active power +/- 0.5 % Apparent power +/- 0.5 % Frequency +/- 0.05 % Power factor +/- 0.005 Current +/- 0.5 % Voltage +/- 0.5 % |
|
accuracy class |
Class 0.5S active energy conforming to IEC 62053-22
|
|
number of outputs |
2 digital
|
|
information displayed |
Tariff (4)
|
|
communication port protocol |
Modbus RTU and ASCII at 9.6, 19.2 and 38.4 kbauds even/odd or none – 2 wires, insulation 2500 V
JBUS |
|
communication port support |
RS485
|
|
data recording |
Event logs
Min/max of instantaneous values Alarm logs Data logs Time stamping Maintenance logs |
|
memory capacity |
256 kB
|
|
connections – terminals |
Voltage circuit: screw terminal block4
Control circuit: screw terminal block2 Current transformer: screw terminal block6 Input/output circuit: screw terminal block6 Relay output: screw terminal block4 Ethernet network: RJ45 connector |
|
mounting mode |
Flush-mounted
|
|
mounting support |
Framework
|
|
standards |
EN 50470-3
IEC 62053-24 IEC 60529 EN 50470-1 UL 61010-1 IEC 62053-22 IEC 61557-12 |
|
product certifications |
CE conforming to IEC 61010-1
CULus conforming to UL 61010-1 |
|
width |
96 mm
|
|
depth |
72 mm
|
|
height |
96 mm
|
|
net weight |
430 g
|