Sale!

1SDA073121R1 E4.2N 3200 Ekip Dip LI 4p WMP

Original price was: ₦1,968,400.00.Current price is: ₦1,958,400.00. 7.5% VAT

E4.2N 3200 Ekip Dip LI 4p WMP

SKU: 1SDA073121R1 Category:

General Information

  • Extended Product Type:
    E4.2N 3200 Ekip Dip LI 4p WMP
  • Product ID:
    1SDA073121R1
  • EAN:
    8015644769710
  • Catalog Description:
    E4.2N 3200 Ekip Dip LI 4p WMP
  • Long Description:
    MOVING PART FOR C.BREAKER SACE EMAX2 E4.2N 3200 FOUR-POLE WITH SOLID-STATE RELEASE IN AC EKIP/DIP-LI R 3200 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED

    Dimensions

    • Product Net Width:
      551 mm
    • Product Net Height:
      425 mm
    • Product Net Depth / Length:
      383 mm
    • Product Net Weight:
      74 kg

    Container Information

    • Package Level 1 Units:
      1 piece
    • Package Level 1 Width:
      515 mm
    • Package Level 1 Height:
      610 mm
    • Package Level 1 Depth / Length:
      785 mm
    • Package Level 1 Gross Weight:
      81 kg
    • Package Level 1 EAN:
      8015644769710

    Environmental

    • RoHS Status:
      Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

    Additional Information

    • Current Type:
      AC
    • Electrical Durability:
      Ue =< 440 V 7000 cycle
      Ue = 500 … 690 V 7000 cycle
      20 cycles per hour
    • Mechanical Durability:
      20000 cycle
      60 cycles per hour
    • Neutral Pole Current ([%Iu]):
      100 %
    • Number of Poles:
      4
    • Power Loss:
      743 W
    • Product Main Type:
      SACE Emax 2
    • Product Name:
      Air Circuit Breaker
    • Product Type:
      Air Circuit Breaker
    • Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics):
      100 %
    • Rated Current (In):
      3200 A
    • Rated Voltage (Ur):
      690 V
    • Rated Impulse Withstand Voltage (Uimp):
      acc. to IEC 60947-2 12 kV
    • Rated Insulation Voltage (Ui):
      AC 1000 V
    • Rated Operational Voltage:
      690 V AC
    • Rated Service Short-Circuit Breaking Capacity (Ics):
      (220 V AC) 66 kA
      (230 V AC) 66 kA
      (380 V AC) 66 kA
      (400 V AC) 66 kA
      (415 V AC) 66 kA
      (440 V AC) 66 kA
      (500 V AC) 66 kA
      (660 V AC) 66 kA
      (690 V AC) 66 kA
    • Rated Short-time Withstand Current (Icw):
      for 1 s 66 kA
      for 3 s 50 kA
    • Rated Ultimate Short-Circuit Breaking Capacity (Icu):
      (400 V AC) 66 kA
      (415 V AC) 66 kA
      (440 V AC) 66 kA
      (500 V AC) 66 kA
      (525 V AC) 66 kA
      (690 V AC) 66 kA
    • Rated Uninterrupted Current (Iu):
      3200 A
    • Release:
      Ekip Dip LI
    • Release Type:
      EL
    • Short-Circuit Performance Level:
      N
    • Standards:
      IEC
    • Sub-type:
      E4.2
    • Version:
      W

    Certificates and Declarations (Document Number)

    Classifications

    • ETIM 4:
      EC000228 – Power circuit-breaker for trafo/generator/installation prot.
    • ETIM 5:
      EC000228 – Power circuit-breaker for trafo/generator/installation prot.
    • ETIM 6:
      EC000228 – Power circuit-breaker for trafo/generator/installation prot.
    • ETIM 7:
      EC000228 – Power circuit-breaker for trafo/generator/installation protection