General Information
-
- Extended Product Type:
- AF205-30-11-13
-
- Product ID:
- 1SFL527002R1311
-
- EAN:
- 7320500480564
-
- Catalog Description:
- AF205-30-11-13 Contactor
-
- Long Description:
- A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-pass and Distribution application up to max 1000 V. Operated with wide control voltage range 100-250 V, 50/60 Hz and DC
Categories
- Products » Low Voltage Products and Systems » Control Products » Contactors » Block Contactors
Technical
-
- Number of Main Contacts NO:
- 3
-
- Number of Main Contacts NC:
- 0
-
- Number of Auxiliary Contacts NO:
- 1
-
- Number of Auxiliary Contacts NC:
- 1
-
- Rated Operational Voltage:
- Main Circuit 1000 V
-
- Rated Frequency (f):
- Main Circuit 50/60 Hz
-
- Conventional Free-air Thermal Current (Ith):
- acc. to IEC 60947-4-1, Open Contactors q = 40 °C 350 A
-
- Rated Operational Current AC-1 (Ie):
- (1000 V) 40 °C 275 A
(1000 V) 55 °C 250 A
(1000 V) 60 °C 250 A
(1000 V) 70 °C 200 A
(690 V) 40 °C 350
(690 V) 55 °C 300
(690 V) 70 °C 240
-
- Rated Operational Current AC-3 (Ie):
- (415 V) 55 °C 205 A
(440 V) 55 °C 205 A
(500 V) 55 °C 186 A
(690 V) 55 °C 165 A
(1000 V) 55 °C 100 A
(380 / 400 V) 55 °C 205 A
(220 / 230 / 240 V) 55 °C 205
-
- Rated Operational Power AC-3 (Pe):
- (415 V) 110 kW
(440 V) 132 kW
(500 V) 132 kW
(690 V) 160 kW
(1000 V) 132 kW
(380 / 400 V) 110 kW
(220 / 230 / 240 V) 55 kW
-
- Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1:
- 8 x Ie AC-3
-
- Rated Making Capacity AC-3 acc. to IEC 60947-4-1:
- 10 x Ie AC-3
-
- Short-Circuit Protective Devices:
- gG Type Fuses 400 A
-
- Rated Short-time Withstand Current (Icw):
- at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1640 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 350 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 670 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 2050 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 947 A
-
- Maximum Breaking Capacity:
- cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3500 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 2500 A
-
- Maximum Electrical Switching Frequency:
- (AC-1) 300 cycles per hour
(AC-2 / AC-4) 150 cycles per hour
(AC-3) 300 cycles per hour
-
- Rated Operational Current DC-1 (Ie):
- (110 V) 2 Poles in Series, 40 °C 275 A
(220 V) 3 Poles in Series, 40 °C 275 A
-
- Rated Operational Current DC-3 (Ie):
- (110 V) 2 Poles in Series, 40 °C 275 A
(220 V) 3 Poles in Series, 40 °C 275 A
-
- Rated Operational Current DC-5 (Ie):
- (110 V) 2 Poles in Series, 40 °C 275 A
(220 V) 3 Poles in Series, 40 °C 275 A
-
- Rated Insulation Voltage (Ui):
- acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
acc. to UL/CSA 600 V
-
- Rated Impulse Withstand Voltage (Uimp):
- Main Circuit 8 kV
-
- Mechanical Durability:
- 5 million
-
- Maximum Mechanical Switching Frequency:
- 300 cycles per hour
-
- Coil Operating Limits:
- (acc. to IEC 60947-4-1) 0.85 x Uc Min. … 1.1 x Uc Max. (at θ ≤ 70 °C)
-
- Rated Control Circuit Voltage (Uc):
- 50 Hz 100 … 250 V
60 Hz 100 … 250 V
DC Operation 100 … 250 V
-
- Coil Consumption:
- Holding at Max. Rated Control Circuit Voltage 50 Hz 7 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 7 V·A
Holding at Max. Rated Control Circuit Voltage DC 2.5 W
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 220 V·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 220 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 190 W
-
- Operate Time:
- Between Coil De-energization and NO Contact Opening 37 … 47 ms
Between Coil Energization and NO Contact Closing 25 … 55 ms
-
- Connecting Capacity Main Circuit:
- Flexible 2 x 50 … 95 mm²
Rigid Al-Cable 1 x 95 … 185 mm²
Rigid Cu-Cable 1 x 6 … 150 mm²
-
- Connecting Capacity Auxiliary Circuit:
- Flexible with Ferrule 1x 0.75 … 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 … 2.5 mm²
Flexible 2×0.75 … 2.5 mm²
Solid 1 x 1 … 4 mm²
Stranded 1 x 1 …. 4 mm²
-
- Degree of Protection:
- acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
-
- Terminal Type:
- Main Circuit: Bars
Technical UL/CSA
-
- Maximum Operating Voltage UL/CSA:
- Main Circuit 1000 V
-
- General Use Rating UL/CSA:
- (600 V AC) 300 A
-
- Horsepower Rating UL/CSA:
- (200 V AC) Three Phase 60 hp
(208 V AC) Three Phase 60 hp
(220 … 240 V AC) Three Phase 75 hp
(440 … 480 V AC) Three Phase 150 hp
(550 … 600 V AC) Three Phase 200 hp
Reviews
There are no reviews yet.