General Information
-
- Extended Product Type:
- A75-40-00 220-230V 50Hz / 230-240V 60Hz
-
- Product ID:
- 1SBL411201R8000
-
- EAN:
- 3471522095800
-
- Catalog Description:
- A75-40-00 220-230V 50Hz / 230-240V 60Hz Contactor
-
- Long Description:
- A75 4-pole contactors are mainly used for controlling non-inductive or slightly inductive loads (i.e. resistance furnaces…) and generally for controlling power circuits up to 690 V AC and 440 V DC. The contactors can also be used for many other applications such lighting… The A… series 4-pole contactors are of the block type design. – Main poles and auxiliary contact blocks: 4 N.O. main poles, front and side-mounted add-on auxiliary contact blocks – Control circuit: AC operated with laminated magnet circuit – Accessories: a wide range of accessories is available.
Categories
- Products » Low Voltage Products and Systems » Control Products » Contactors » Block Contactors
Technical
-
- Number of Main Contacts NO:
- 4
-
- Number of Main Contacts NC:
- 0
-
- Number of Auxiliary Contacts NO:
- 0
-
- Number of Auxiliary Contacts NC:
- 0
-
- Standards:
- Devices complying with international standards IEC 947-1 / 947-4-1, and European standards EN 60 947-1 / 60 947-4-1. Electromagnetic compatibility (EMC) acc. to amendment A11 to IEC 947-1, EN 60 947-1 and amendment 2 to IEC 947-4-1
-
- Rated Operational Voltage:
- Main Circuit 1000 V
-
- Conventional Free-air Thermal Current (Ith):
- acc. to IEC 60947-4-1, Open Contactors q = 40 °C 125 A
-
- Rated Operational Current AC-1 (Ie):
- (690 V) 40 °C 125
(690 V) 55 °C 105
(690 V) 70 °C 85
-
- Rated Operational Current AC-3 (Ie):
- (415 V) 55 °C 72 A
(440 V) 55 °C 70 A
(500 V) 55 °C 65 A
(690 V) 55 °C 46 A
(1000 V) 55 °C 28 A
(380 / 400 V) 55 °C 75 A
(220 / 230 / 240 V) 55 °C 75
-
- Rated Operational Power AC-3 (Pe):
- (415 V) 40 kW
(440 V) 40 kW
(500 V) 45 kW
(690 V) 40 kW
(380 / 400 V) 37 kW
(220 / 230 / 240 V) 22 kW
-
- Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1:
- 8 x Ie AC-3
-
- Rated Making Capacity AC-3 acc. to IEC 60947-4-1:
- 10 x Ie AC-3
-
- Short-Circuit Protective Devices:
- gG Type Fuses 160 A
-
- Maximum Breaking Capacity:
- cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1300 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 630 A
-
- Maximum Electrical Switching Frequency:
- (AC-1) 600 cycles per hour
(AC-2 / AC-4) 150 cycles per hour
(AC-3) 600 cycles per hour
-
- Rated Insulation Voltage (Ui):
- acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
acc. to UL/CSA 600 V
-
- Rated Impulse Withstand Voltage (Uimp):
- 8 kV
-
- Mechanical Durability:
- 10 million
-
- Maximum Mechanical Switching Frequency:
- 3600 cycles per hour
-
- Rated Control Circuit Voltage (Uc):
- 50 Hz 220 … 230 V
60 Hz 230 … 240 V
-
- Coil Consumption:
- Average Holding Value 50 / 60 Hz 18 5.5 V·A
Average Pull-in Value 50 Hz 190 V·A
Average Pull-in Value 60 Hz 180 V·A
Holding at Max. Rated Control Circuit Voltage 50 Hz 18 5.5 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 18 5.5 V·A
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 180 V·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 210 V·A
-
- Operate Time:
- Between Coil De-energization and NO Contact Opening 4 … 11 ms
Between Coil Energization and NO Contact Closing 8 … 27 ms
-
- Connecting Capacity Main Circuit:
- Flexible with Cable End 6 … 16 mm²
Rigid Cable 6 … 25 mm²
-
- Connecting Capacity Auxiliary Circuit:
- Flexible with Cable End 0.75 … 2.5 mm²
Rigid Cable 1 … 4 mm²
-
- Degree of Protection:
- acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
-
- Connecting Terminals (delivered in open position) Main Poles:
- M 6 (+,-) pozidriv 2 screws with 1x (13 x 10 mm) connector
-
- Terminal Type:
- Screw Terminals
Reviews