General Information
-
- Extended Product Type:
- A30-30-10 230-240V 50Hz / 240-260V 60Hz
-
- Product ID:
- 1SBL281001R8810
-
- EAN:
- 3471522071880
-
- Catalog Description:
- A30-30-10 230-240V 50Hz / 240-260V 60Hz Contactor
-
- Long Description:
- A30 contactors are mainly used for controlling 3-phase motors and generally for controlling power circuits up to 690 V AC or 220 V DC. The contactors can also be used for many other applications such as isolation, capacitor switching, lighting. The A… series 1-stack 3-pole contactors are of the block type design. – Main poles and auxiliary contact blocks: 3 main poles, 1 built-in auxiliary contact, front and side-mounted add-on auxiliary contact blocks – Control circuit: AC operated with laminated magnet circuit – Accessories: a wide range of accessories is available.
Categories
- Products » Low Voltage Products and Systems » Control Products » Contactors » Across the Line Contactors
Technical
-
- Number of Main Contacts NO:
- 3
-
- Number of Main Contacts NC:
- 0
-
- Number of Auxiliary Contacts NO:
- 1
-
- Number of Auxiliary Contacts NC:
- 0
-
- Standards:
- Devices complying with international standards IEC 947-1 / 947-4-1, and European standards EN 60 947-1 / 60 947-4-1. Electromagnetic compatibility (EMC) acc. to amendment A11 to IEC 947-1, EN 60 947-1 and amendment 2 to IEC 947-4-1
-
- Rated Operational Voltage:
- Main Circuit 690 V
-
- Rated Frequency (f):
- Supply Circuit 50 60 Hz
-
- Conventional Free-air Thermal Current (Ith):
- acc. to IEC 60947-4-1, Open Contactors q = 40 °C 65 A
acc. to IEC 60947-5-1, q = 40 °C 16 A
-
- Rated Operational Current AC-1 (Ie):
- (690 V) 40 °C 55
(690 V) 55 °C 55
(690 V) 70 °C 39
-
- Rated Operational Current AC-3 (Ie):
- (415 V) 55 °C 32 A
(440 V) 55 °C 32 A
(500 V) 55 °C 28 A
(690 V) 55 °C 21 A
(380 / 400 V) 55 °C 32 A
(220 / 230 / 240 V) 55 °C 33
-
- Rated Operational Power AC-3 (Pe):
- (415 V) 15 kW
(440 V) 18.5 kW
(500 V) 18.5 kW
(690 V) 18.5 kW
(380 / 400 V) 15 kW
(220 / 230 / 240 V) 9 kW
-
- Rated Operational Power AC-6b (Pe):
- (230 / 240 V) 40 °C, 50 / 60 Hz 13 kvar
(230 / 240 V) 55 °C, 50 / 60 Hz 13 kvar
(230 / 240 V) 70 °C, 50 / 60 Hz 11 kvar
(400 / 415 V) 40 °C, 50 / 60 Hz 22 kvar
(400 / 415 V) 70 °C, 50 / 60 Hz 18.5 kvar
(400 / 415 V) 55 °C, 50 / 60 Hz 22 kvar
(440 V) 40 °C, 50 / 60 Hz 24 kvar
(440 V) 55 °C, 50 / 60 Hz 24 kvar
(440 V) 70 °C, 50 / 60 Hz 20.5 kvar
(500 / 550 V), 40 °C, 50 / 60 Hz 28 kvar
(500 / 550 V) 55 °C, 50 / 60 Hz 28 kvar
(500 / 550 V) 70 °C, 50 / 60 Hz 23 kvar
(690 V) 40 °C, 50 / 60 Hz 38 kvar
(690 V) 55 °C, 50 / 60 Hz 38 kvar
(690 V) 70 °C, 50 / 60 Hz 32 kvar
-
- Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1:
- 8 x Ie AC-3
-
- Rated Making Capacity AC-3 acc. to IEC 60947-4-1:
- 10 x Ie AC-3
-
- Rated Operational Current AC-15 (Ie):
- (500 V) 2 A
(690 V) 2 A
(24 / 127 V) 6 A
(220 / 240 V) 4 A
(380 / 400 V) 3 A
-
- Short-Circuit Protective Devices:
- Auxiliary Circuit – gG Type Fuses 10 A
gG Type Fuses 63 A
-
- Maximum Breaking Capacity:
- cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 820 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 340 A
-
- Maximum Electrical Switching Frequency:
- (AC-1) 600 cycles per hour
(AC-2 / AC-4) 300 cycles per hour
(AC-3) 1200 cycles per hour
-
- Rated Operational Current DC-13 (Ie):
- (24 V) 6 / 144 A
(48 V) 2.8 / 134 A
(72 V) 2 / 144 A
(125 V) 1.1 / 138 A
(250 V) 0.55 / 138 A
-
- Rated Insulation Voltage (Ui):
- acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
acc. to UL/CSA 600 V
-
- Rated Impulse Withstand Voltage (Uimp):
- 8 kV
-
- Mechanical Durability:
- 10 million
-
- Maximum Mechanical Switching Frequency:
- 3600 cycles per hour
-
- Rated Control Circuit Voltage (Uc):
- 50 Hz 230 … 240 V
60 Hz 240 … 260 V
-
- Coil Consumption:
- Average Holding Value 50 / 60 Hz 12 3 V·A
Average Pull-in Value 50 Hz 125 V·A
Average Pull-in Value 60 Hz 120 V·A
-
- Operate Time:
- Between Coil De-energization and NO Contact Opening 4 … 11 ms
Between Coil Energization and NO Contact Closing 8 … 21 ms
-
- Connecting Capacity Main Circuit:
- Flexible with Cable End 2.5 … 10 mm²
Rigid Cable 2.5 … 16 mm²
-
- Connecting Capacity Auxiliary Circuit:
- Flexible with Cable End 0.75 … 2.5 mm²
Rigid Cable 1 … 4 mm²
-
- Degree of Protection:
- acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
-
- Connecting Terminals (delivered in open position) Main Poles:
- M 5 (+,-) pozidriv 2 screw with 2x (5.6×6.5 mm) connector
-
- Terminal Type:
- Screw Terminals
Reviews