General Information
-
- Extended Product Type:
- T7S 1250 PR231/P LS/I In=1250A 3p F F
-
- Product ID:
- 1SDA062866R1
-
- EAN:
- 8015644654153
-
- Catalog Description:
- T7S 1250 PR231/P LS/I In=1250A 3p F F
-
- Long Description:
- C.BREAKER TMAX T7S 1250 FIXED THREE-POLE WITH FRONT TERMINALS AND LEVER OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR231/P-LS/I R 1250
Dimensions
-
- Product Net Width:
- 210 mm
-
- Product Net Height:
- 268 mm
-
- Product Net Depth / Length:
- 154 mm
-
- Product Net Weight:
- 14.369 kg
Additional Information
-
- Electrical Durability:
- 2000 cycle
60 cycles per hour
-
- Mechanical Durability:
- 10000 cycle
60 cycles per hour
-
- Number of Poles:
- 3
-
- Power Loss:
- at Rated Operating Conditions per Pole 47 W
-
- Product Main Type:
- SACE Tmax T
-
- Product Name:
- Moulded Case Circuit Breaker
-
- Product Type:
- CB
-
- Rated Current (In):
- Main Circuit 1250 A
-
- Rated Impulse Withstand Voltage (Uimp):
- 8 kV
-
- Rated Insulation Voltage (Ui):
- 1000 V
-
- Rated Operational Voltage:
- 690 V AC
-
- Rated Service Short-Circuit Breaking Capacity (Ics):
- (220 V AC) 85 kA
(230 V AC) 85 kA
(380 V AC) 50 kA
(400 V AC) 50 kA
(415 V AC) 50 kA
(440 V AC) 50 kA
(500 V AC) 40 kA
(690 V AC) 30 kA
-
- Rated Short-time Withstand Current (Icw):
- for 1 s 20 kA
-
- Rated Ultimate Short-Circuit Breaking Capacity (Icu):
- (220 V AC) 85 kA
(230 V AC) 85 kA
(380 V AC) 50 kA
(400 V AC) 50 kA
(415 V AC) 50 kA
(440 V AC) 50 kA
(500 V AC) 40 kA
(690 V AC) 30 kA
-
- Rated Uninterrupted Current (Iu):
- 1250 A
-
- Release:
- PR231/P-LS/I
-
- Release Type:
- EL
-
- Short-Circuit Performance Level:
- S
-
- Standards:
- IEC
-
- Sub-type:
- T7
-
- Suitable For:
- T7
-
- Suitable for Product Class:
- Moulded Case Circuit Breakers
-
- Terminal Connection Type:
- Fixed Circuit-Breakers
Front
-
- Version:
- F
Reviews