General Information
-
- Extended Product Type:
- MS116-0.63
-
- Product ID:
- 1SAM250000R1004
-
- EAN:
- 4013614320279
-
- Catalog Description:
- MS116-0.63 Manual Motor Starter
-
- Long Description:
- The MS116-0.63 manual motor starter (also known as motor protection circuit breaker or manual motor protector) is a compact 45 mm width device with a rated operational current of Ie = 0.63 A. This device is used to manually switch on and off motors and to protect them reliably and without the need for a fuse from short-circuits, overload and phase failures. The manual motor starter offers a rated service short-circuit breaking capacity Ics = 50 kA at 400 VAC and trip class 10A. Further features are the build-in disconnect function, temperature compensation, trip-free mechanism and a rotary handle with a clear switch position indication. The manual motor starter is suitable for three- and single-phase applications. Auxiliary contacts, signaling contacts, undervoltage releases, shunt trips, 3-phase bus bars, power in-feed blocks and locking devices for protection against unauthorized changes are available as accessory.
Categories
- Products » Low Voltage Products and Systems » Circuit Breakers » Manual Motor Starters
- Products » Low Voltage Products and Systems » Control Products » Manual Motor Starters » Manual Motor Starters
- Parts & Services » Drives » Medium voltage AC drives » Industrial drives » ACS1000
- Parts & Services » Drives » Medium voltage AC drives » Industrial drives » ACS2000
-
- Data Sheet, Technical Information:
- 2CDC131025D0201
-
- Instructions and Manuals:
- 2CDC131011M6802
-
- Instructions and Manuals (Part 2):
- 2CDC131060M0202
-
- Time-Current Characteristic Curve:
- 1SAM200505F0104
-
- I²t Characteristic:
- 1SAM200507F0001
1SAM200507F0002
1SAM200507F0003
-
- Cut-off Current Characteristic:
- 1SAM200508F0001
1SAM200508F0002
1SAM200508F0003
-
- Dimension Diagram:
- 1SAM200422F0001
Technical
-
- Rated Service Short-Circuit Breaking Capacity (Ics):
- (230 V AC) 50 kA
(400 V AC) 50 kA
(440 V AC) 50 kA
(500 V AC) 30 kA
(690 V AC) 30 kA
-
- Rated Ultimate Short-Circuit Breaking Capacity (Icu):
- (230 V AC) 100 kA
(400 V AC) 100 kA
(440 V AC) 100 kA
(500 V AC) 100 kA
(690 V AC) 100 kA
-
- Rated Instantaneous Short-Circuit Current Setting (Ii):
- 7.9 A
-
- Setting Range:
- 0.40 … 0.63 A
-
- Rated Operational Power AC-3 (Pe):
- (400 V) Three Phase 0.18 kW
-
- Rated Operational Power AC-3e (Pe):
- (400 V) Three Phase 0.18 kW
-
- Rated Operational Voltage:
- Main Circuit 690 V AC
-
- Rated Operational Current (Ie):
- 0.63 A
-
- Rated Operational Current AC-3 (Ie):
- 0.63 A
-
- Rated Operational Current AC-3e (Ie):
- 0.63 A
-
- Rated Frequency (f):
- Main Circuit 50 Hz
Main Circuit 60 Hz
-
- Rated Impulse Withstand Voltage (Uimp):
- Main Circuit 6 kV
-
- Rated Insulation Voltage (Ui):
- 690 V
-
- Power Loss:
- at Rated Operating Conditions per Pole 0.7 … 1.7 W
-
- Number of Poles:
- 3
-
- Conventional Free-air Thermal Current (Ith):
- Main Circuit 0.63 A
-
- Degree of Protection:
- Housing IP20
Main Circuit Terminals IP10
-
- Pollution Degree:
- 3
-
- Electrical Durability:
- 100000 cycle
-
- Mechanical Durability:
- 100000 cycle
-
- Terminal Type:
- Screw Terminals
-
- Connecting Capacity Main Circuit:
- Flexible with Ferrule 1/2x 0.75 … 2.5 mm²
Flexible with Insulated Ferrule 1/2x 0.75 … 2.5 mm²
Flexible 1/2x 0.75 … 2.5 mm²
Rigid 1/2x 1 … 4 mm²
-
- Tightening Torque:
- Main Circuit 0.8 … 1.2 N·m
-
- Wire Stripping Length:
- Main Circuit 9 mm
-
- Recommended Screw Driver:
- Pozidriv 2
-
- Mounting Position:
- Position 1 to 6
-
- Mounting on DIN Rail:
- TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
-
- Minimum Mounting Distance:
- Electrical Conductive Board, Horizontal – Up to 400 V 0 mm
Electrical Conductive Board, Horizontal – Up to 690 V 1.5 mm
Electrical Conductive Board, Vertical 75 mm
Other Device Same Type, Horizontal 0 mm
Other Device Same Type, Vertical 150 mm
-
- Actuator Type:
- Rotary Handle
-
- Contact Position Indication:
- ON / OFF
-
- Standards:
- IEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
UL 60947-1
UL 60947-4-1
Technical UL/CSA
-
- Short-Circuit Current Rating (SCCR):
- Any UL Listed Fuses or Circuit-Breakers, Group Installations (480 V AC) 30 kA
Any UL Listed Fuses or Circuit-Breakers, Group Installations (600 V AC) 5 kA
Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (480 V AC) 30 kA
Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (600 V AC) 5 kA
-
- Maximum Operating Voltage UL/CSA:
- Main Circuit 600 V AC
-
- Ampere Rating UL/CSA:
- 0.63 A
-
- Full Load Amps Motor Use:
- (110 … 120 V AC) Three Phase 0.63 A
(200 V AC) Three Phase 0.63 A
(208 V AC) Three Phase 0.63 A
(220 … 240 V AC) Three Phase 0.63 A
(440 … 480 V AC) Three Phase 0.63 A
(550 … 600 V AC) Three Phase 0.63 A
-
- Locked Rotor Amps:
- (110 … 120 V AC) Three Phase 3.78 A
(200 V AC) Three Phase 3.78 A
(208 V AC) Three Phase 3.78 A
(220 … 240 V AC) Three Phase 3.78 A
(440 … 480 V AC) Three Phase 3.78 A
(550 … 600 V AC) Three Phase 3.78 A
-
- General Use Rating UL/CSA:
- (600 V AC) 0.63 A
-
- Connecting Capacity Main Circuit UL/CSA:
- Flexible 1/2x 16-12 AWG
Stranded 1/2x 16-12 AWG
-
- Tightening Torque UL/CSA:
- Main Circuit 10 in·lb
Reviews
There are no reviews yet.