- Data Sheet, Technical Information:
- 2CDC131083D0201
-
- Instructions and Manuals:
- 2CDC131081M6801
-
- Instructions and Manuals (Part 2):
- 2CDC131060M0202
-
- Time-Current Characteristic Curve:
- 1SAM400505F0006
-
- I²t Characteristic:
- 1SAM400506F0001
-
- Cut-off Current Characteristic:
- 1SAM400507F0001
-
- Dimension Diagram:
- 1SAM400401F0001
Dimensions
-
- Product Net Width:
- 55 mm
-
- Product Net Height:
- 142.65 mm
-
- Product Net Depth / Length:
- 122.1 mm
-
- Product Net Weight:
- 0.97 kg
Technical
-
- Rated Service Short-Circuit Breaking Capacity (Ics):
- (230 V AC) 30 kA
(250 V DC) 3 Poles in Series 100 kA
(400 V AC) 30 kA
(440 V AC) 30 kA
(500 V AC) 20 kA
(690 V AC) 6 kA
-
- Rated Ultimate Short-Circuit Breaking Capacity (Icu):
- (230 V AC) 50 kA
(250 V DC) 100 kA
(400 V AC) 50 kA
(440 V AC) 45 kA
(500 V AC) 20 kA
(690 V AC) 8 kA
-
- Rated Instantaneous Short-Circuit Current Setting (Ii):
- 810 A
-
- Setting Range:
- 40 … 54 A
-
- Rated Operational Power AC-3 (Pe):
- (400 V) Three Phase 22 kW
-
- Rated Operational Power AC-3e (Pe):
- (400 V) Three Phase 22 kW
-
- Rated Operational Voltage:
- Main Circuit 690 V AC
Main Circuit 250 V DC
-
- Rated Operational Current (Ie):
- 54 A
-
- Rated Operational Current AC-3 (Ie):
- 54 A
-
- Rated Operational Current AC-3e (Ie):
- 54 A
-
- Rated Operational Current DC-5 (Ie):
- 54 A
-
- Rated Frequency (f):
- Main Circuit 50 Hz
Main Circuit 60 Hz
-
- Rated Impulse Withstand Voltage (Uimp):
- Main Circuit 8 kV
-
- Rated Insulation Voltage (Ui):
- 1000 V
-
- Power Loss:
- at Rated Operating Conditions per Pole 3.84 … 6.99 W
-
- Number of Poles:
- 3