- The TF65-40 thermal overload relay is an economic electromechanical protection device for the main circuit. It offers reliable and fast protection for motors in the event of overload or phase failure. The device has trip class 10. Further features are the temperature compensation, trip contact (NC), signal contact (NO), automatic- or manual reset selectable, trip-free mechanism, STOP function and a trip indication. The overload relays are connected directly to the block contactors. Single mounting kits are available as accessory.
Categories
- Products » Low Voltage Products and Systems » Control Products » Contactors » Thermal Overload Relays
Technical
-
- Setting Range:
- 30 … 40 A
-
- Rated Operational Voltage:
- Auxiliary Circuit 600 V AC/DC
Main Circuit 690 V AC
Main Circuit 440 V DC
-
- Rated Operational Current (Ie):
- 40 A
-
- Rated Operational Current AC-3 (Ie):
- 40 A
-
- Rated Frequency (f):
- Auxiliary Circuit 50 Hz
Auxiliary Circuit 60 Hz
Auxiliary Circuit DC
Main Circuit 50 Hz
Main Circuit 60 Hz
-
- Rated Impulse Withstand Voltage (Uimp):
- Auxiliary Circuit 6 kV
Main Circuit 8 kV
-
- Rated Insulation Voltage (Ui):
- 690 V
-
- Number of Poles:
- 3
-
- Number of Auxiliary Contacts NC:
- 1
-
- Number of Auxiliary Contacts NO:
- 1
-
- Number of Protected Poles:
- 3
-
- Conventional Free-air Thermal Current (Ith):
- Auxiliary Circuit NC 6 A
Auxiliary Circuit NO 4 A
-
- Rated Operational Current AC-15 (Ie):
- (120 V) NC 3 A
(120 V) NO 0.5 A
(240 V) NC 3 A
(240 V) NO 0.5 A
(400 V) NC 0.75 A
(400 V) NO 0.5 A
(500 V) NC 0.75 A
(500 V) NO 0.5 A
-
- Rated Operational Current DC-13 (Ie):
- (125 V) NC 0.55 A
(125 V) NO 0.55 A
(24 V) NC 1.25 A
(24 V) NO 1.25 A
(250 V) NC 0.27 A
(250 V) NO 0.27 A
(500 V) NC 0.15 A
(500 V) NO 0.15 A
(60 V) NC 0.55 A
(60 V) NO 0.55 A
-
- Degree of Protection:
- Housing IP20
Main Circuit Terminals IP10
-
- Pollution Degree:
- 3
-
- Connecting Capacity Auxiliary Circuit:
- Flexible with Ferrule 1/2x 0.75 … 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75 … 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 … 1.5 mm²
Flexible 1/2x 0.75 … 1 mm²
Flexible 1/2x 1 … 2.5 mm²
Rigid 1/2x 0.75 … 4 mm²
-
- Connecting Capacity Main Circuit:
- Flexible with Ferrule 1/2x 2.5 … 10 mm²
Flexible with Ferrule 1x 2.5 … 35 mm²
Flexible with Insulated Ferrule 1x 2.5 … 35 mm²
Flexible with Insulated Ferrule 1/2x 2.5 … 10 mm²
Flexible 1/2x 2.5 … 16 mm²
Flexible 1x 2.5 … 35 mm²
Rigid 1/2x 2.5 … 16 mm²
Rigid 1x 2.5 … 35 mm²
-
- Tightening Torque:
- Auxiliary Circuit 1 … 1.2 N·m
Main Circuit 4.0 … 4.5 N·m
-
- Wire Stripping Length:
- Auxiliary Circuit 9 mm
Main Circuit 17 mm
-
- Recommended Screw Driver:
- Auxiliary Circuit Pozidriv 2
Main Circuit Pozidriv 2
-
- Mounting Position:
- Position 1 to 6
-
- Power Loss:
- at Rated Operating Conditions per Pole 2.1 … 3.7 W
-
- Suitable For:
- AF40
AF52
AF65
-
- Standards:
- IEC/EN 60947-1
IEC/EN 60947-4-1
IEC/EN 60947-5-1
UL 60947-1
UL 60947-4-1
Technical UL/CSA
-
- Maximum Operating Voltage UL/CSA:
- Main Circuit 600 V AC
-
- Ampere Rating UL/CSA:
- 40 A
-
- Contact Rating UL/CSA:
- (NC:) B600
(NC:) Q600
(NO:) Q600
(NO:) D300
-
- Connecting Capacity Main Circuit UL/CSA:
- Flexible 1x 12-2 AWG
Flexible 2x 12-6 AWG
Stranded 1x 12-2 AWG
Stranded 2x 12-6 AWG
-
- Connecting Capacity Auxiliary Circuit UL/CSA:
- Flexible 1/2x 18-12 AWG
Stranded 1/2x 18-12 AWG
- Tightening Torque UL/CSA:Auxiliary Circuit 9 … 11 in·lb
Main Circuit 35 … 40 in·lb