General Information
-
- Extended Product Type:
- AF30-30-00-13
-
- Product ID:
- 1SBL277001R1300
-
- EAN:
- 3471523111233
-
- Catalog Description:
- AF30-30-00-13 100-250V50/60HZ-DC Contactor
-
- Long Description:
- AF30 contactors are used for controlling power circuits up to 690 V AC and 220 V DC. They are mainly used for controlling 3-phase motors, non-inductive or slightly inductive loads. AF… contactors include an electronic coil interface accepting a wide control voltage Uc min. … Uc max. Only four coils cover control voltages between 24…500 V 50/60 Hz or 20…500 V DC. AF contactors can manage large control voltage variations. One coil can be used for different control voltages used worldwide without any coil change. AF contactors have built-in surge protection and do not require additional surge suppressors. The AF… series 1-stack 3-pole contactors are of the block type design. – Main poles and auxiliary contact blocks: 3 main poles, front and side-mounted add-on auxiliary contact blocks (mechanically-linked auxiliary contacts compliant with Annex L of IEC 60947-5-1. N.C. mirror contacts compliant with Annex F of IEC 60947-4-1) – Control circuit: AC or DC operated – Accessories: a wide range of accessories is available.
Categories
- Products » Low Voltage Products and Systems » Control Products » Contactors » Block Contactors
Technical
-
- Number of Main Contacts NO:
- 3
-
- Number of Main Contacts NC:
- 0
-
- Number of Auxiliary Contacts NO:
- 0
-
- Number of Auxiliary Contacts NC:
- 0
-
- Standards:
- IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1, UL 508, CSA C22.2 N°14
-
- Rated Operational Voltage:
- Main Circuit 690 V
-
- Rated Frequency (f):
- Main Circuit 50 / 60 Hz
-
- Conventional Free-air Thermal Current (Ith):
- acc. to IEC 60947-4-1, Open Contactors q = 40 °C 50 A
-
- Rated Operational Current AC-1 (Ie):
- (690 V) 40 °C 50
(690 V) 60 °C 42 A
(690 V) 70 °C 37
-
- Rated Operational Current AC-3 (Ie):
- (415 V) 60 °C 32 A
(440 V) 60 °C 32 A
(500 V) 60 °C 28 A
(690 V) 60 °C 21 A
(380 / 400 V) 60 °C 32 A
(220 / 230 / 240 V) 60 °C 33 A
-
- Rated Operational Power AC-3 (Pe):
- (400 V) 15 kW
(415 V) 15 kW
(440 V) 18.5 kW
(500 V) 18.5 kW
(690 V) 18.5 kW
(380 / 400 V) 15 kW
(220 / 230 / 240 V) 9 kW
-
- Rated Short-time Withstand Current (Icw):
- at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 350 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 50 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 150 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 700 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 225 A
for 1 s -empty- A
-
- Maximum Breaking Capacity:
- cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 500 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 200 A
-
- Maximum Electrical Switching Frequency:
- (AC-1) 600 cycles per hour
(AC-2 / AC-4) 150 cycles per hour
(AC-3) 1200 cycles per hour
-
- Rated Insulation Voltage (Ui):
- acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
acc. to UL/CSA 600 V
-
- Rated Impulse Withstand Voltage (Uimp):
- 6 kV
-
- Maximum Mechanical Switching Frequency:
- 3600 cycles per hour
-
- Rated Control Circuit Voltage (Uc):
- 50 Hz 100 … 250 V
50 Hz / 60 Hz 100 … 250 V
60 Hz 100 … 250 V
DC Operation 100 … 250 V
-
- Operate Time:
- Between Coil De-energization and NC Contact Closing 13 … 98 ms
Between Coil De-energization and NO Contact Opening 11 … 95 ms
Between Coil Energization and NC Contact Opening 38 … 90 ms
Between Coil Energization and NO Contact Closing 40 … 95 ms
-
- Connecting Capacity Main Circuit:
- Flexible with Ferrule 1/2x 1.5 … 10 mm²
Flexible with Insulated Ferrule 1x 1.5 … 10 mm²
Flexible with Insulated Ferrule 2x 1.5 … 4 mm²
Rigid 1/2x 2.5 … 10 mm²
-
- Connecting Capacity Control Circuit:
- Flexible with Ferrule 1/2x 0.75 … 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75 … 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 … 1.5 mm²
Rigid 1/2x 1 … 2.5 mm²
-
- Wire Stripping Length:
- Control Circuit 10 mm
Main Circuit 14 mm
-
- Degree of Protection:
- acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
-
- Terminal Type:
- Screw Terminals
Technical UL/CSA
-
- General Use Rating UL/CSA:
- (600 V AC) 50 A
-
- Horsepower Rating UL/CSA:
- (120 V AC) Single Phase 2 hp
(200 … 208 V AC) Three Phase 10 hp
(220 … 240 V AC) Three Phase 10 hp
(240 V AC) Single Phase 5 hp
(440 … 480 V AC) Three Phase 20 hp
(550 … 600 V AC) Three Phase 25 hp
-
- Tightening Torque UL/CSA:
- Control Circuit 11 IA
Main Circuit 22 IA
Reviews