General Information
-
- Extended Product Type:
- E1B800PR121/P-LIIn=800A3pWMP
-
- Product ID:
- 1SDA055616R1
-
- EAN:
- 8015644569563
-
- Catalog Description:
- E1B 800 PR121/P-LI In=800A 3p W MP
-
- Long Description:
- SACE EMAX MOVING PART FOR CIRCUIT-BREAKER E1B 800A THRE-POLE OVERCURRENT RELEASE PR121/P-LI R800 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED
Dimensions
-
- Product Net Width:
- 324 mm
-
- Product Net Height:
- 461 mm
-
- Product Net Depth / Length:
- 396.5 mm
-
- Product Net Weight:
- 44 kg
Container Information
-
- Package Level 1 Units:
- 1 piece
-
- Package Level 1 Width:
- 515 mm
-
- Package Level 1 Height:
- 600 mm
-
- Package Level 1 Depth / Length:
- 515 mm
-
- Package Level 1 Gross Weight:
- 55 kg
-
- Package Level 1 EAN:
- 8015644569563
Additional Information
-
- Current Type:
- AC
-
- Electrical Durability:
- Ue =< 440 V 10000 cycle
Ue = 500 … 690 V 10000 cycle
30 cycles per hour
-
- Mechanical Durability:
- 25000 cycle
60 cycles per hour
-
- Number of Poles:
- 3
-
- Power Loss:
- 95 W
-
- Product Main Type:
- SACE Emax
-
- Product Name:
- Air Circuit Breaker
-
- Product Type:
- Air Circuit Breaker
-
- Rated Current (In):
- 800 A
-
- Rated Voltage (Ur):
- 690 V
-
- Rated Impulse Withstand Voltage (Uimp):
- 12 kV
-
- Rated Insulation Voltage (Ui):
- 1000 V
-
- Rated Operational Current (Ie):
- 800 A
-
- Rated Operational Voltage:
- 690 V AC
-
- Rated Service Short-Circuit Breaking Capacity (Ics):
- (220 V AC) 42 kA
(230 V AC) 42 kA
(400 V AC) 42 kA
(415 V AC) 42 kA
(440 V AC) 42 kA
(500 V AC) 42 kA
(660 V AC) 42 kA
(380 V AC) 42 kA
(690 V AC) 42 kA
-
- Rated Short-time Withstand Current (Icw):
- for 1 s 42 kA
for 3 s 36 kA
-
- Rated Ultimate Short-Circuit Breaking Capacity (Icu):
- (220 V AC) 42 kA
(230 V AC) 42 kA
(400 V AC) 42 kA
(415 V AC) 42 kA
(440 V AC) 42 kA
(500 V AC) 42 kA
(660 V AC) 42 kA
(380 V AC) 42 kA
(690 V AC) 42 kA
-
- Rated Uninterrupted Current (Iu):
- 800 A
-
- Release:
- PR121/P-LI
-
- Release Type:
- EL
-
- Short-Circuit Performance Level:
- B
-
- Standards:
- IEC
-
- Sub-type:
- E1
-
- Terminal Connection Type:
- Withdrawable Circuit-Breakers
-
- Version:
- W
Certificates and Declarations (Document Number)
-
- Data Sheet, Technical Information:
- 1SDC200006D0209
-
- Declaration of Conformity – CE:
- 1SDL000165R0013
-
- Instructions and Manuals:
- 1SDH000460R0002
Classifications
-
- ETIM 4:
- EC000228 – Power circuit-breaker for trafo/generator/installation prot.
-
- ETIM 5:
- EC000228 – Power circuit-breaker for trafo/generator/installation prot.
-
- ETIM 6:
- EC000228 – Power circuit-breaker for trafo/generator/installation prot.
-
Reviews