range |
ComPact
|
|
---|---|---|
product name |
ComPact NS
|
|
range of product |
ComPact NS630b…1600
|
|
device short name |
Compact NS800N
|
|
product or component type |
Circuit breaker
|
|
device application |
Distribution
|
|
Number of poles |
3P
|
|
protected poles description |
3d
|
|
(In) rated current up to 65 °C |
800 A at 50 °C
|
|
[Ue] rated operational voltage |
690 V AC 50/60 Hz
|
|
network type |
AC
|
|
network frequency |
50/60 Hz
|
|
suitability for isolation |
Yes conforming to EN/IEC 60947-2
|
|
utilisation category |
Category B
|
|
[Icu] rated ultimate short-circuit breaking capacity |
30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 |
|
Performance level |
N 50 kA 415 V AC
|
|
trip unit name |
Micrologic 2.0
|
|
trip unit technology |
Electronic
|
|
trip unit protection functions |
LI
|
|
control type |
Rotary handle
Toggle |
|
Circuit breaker mounting mode |
Fixed
|
[Ui] rated insulation voltage |
800 V AC 50/60 Hz conforming to IEC 60947-2
|
|
---|---|---|
[Uimp] rated impulse withstand voltage |
8 kV conforming to IEC 60947-2
|
|
[Ics] rated service short-circuit breaking capacity |
30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Icw] rated short-time withstand current |
19.2 kA 1 s conforming to IEC 60947-2
|
|
mechanical durability |
10000 cycles
|
|
electrical durability |
2000 cycles at 690 V In
4000 cycles at 690 V In/2 5000 cycles at 440 V In 6000 cycles at 440 V In/2 |
|
power losses |
15 W
|
|
mounting support |
Backplate
|
|
upside connection |
Front
|
|
downside connection |
Front
|
|
connection pitch |
70 mm
|
|
protection type |
L : for overload protection (long time)
I : for instantaneous short-circuit protection |
|
trip unit rating |
800 A at 50 °C
|
|
Long-time pick-up adjustment type Ir (thermal protection) |
Adjustable 9 settings
|
|
[Ir] long-time protection pick-up adjustment range |
0.4…1 x In
|
|
Long-time protection delay adjustment type tr |
Adjustable 9 settings
|
|
[tr] long-time protection delay adjustment range |
12.5…600 s at 1.5 x Ir
0.5…24 s at 6 x Ir 0.7…16.6 s at 7.2 x Ir |
|
thermal memory |
20 mn
|
|
Instantaneous protection pick-up adjustment type Ii |
Adjustable
|
|
[Ii] instantaneous protection pick-up adjustment range |
1.5…10 x Ir
|
|
earth-leakage protection |
Without
|
|
auxiliary contact composition |
1 NO/NC
|
|
local signalling |
4 LEDs (red) for fault indication
1 LED (yellow) for overload |
|
Width (W) |
210 mm
|
|
Height (H) |
327 mm
|
|
Depth (D) |
147 mm
|
|
net weight |
14 kg
|