range |
Acti 9
|
|
---|---|---|
product name |
Acti 9 C60H-DC
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
C60H-DC
|
|
device application |
Distribution
|
|
poles description |
1P
|
|
number of protected poles |
1
|
|
[In] rated current |
32 A at 25 °C
|
|
network type |
DC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10 kA Icu at 220 V DC conforming to EN 60947-2
10 kA Icu at 220 V DC conforming to IEC 60947-2 6 kA Icu at 250 V DC conforming to EN 60947-2 6 kA Icu at 250 V DC conforming to IEC 60947-2 20 kA Icu at 110 V DC conforming to EN 60947-2 20 kA Icu at 110 V DC conforming to IEC 60947-2 |
|
utilisation category |
Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to IEC 60947-2
Yes conforming to EN 60947-2 |
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
250 V DC
|
|
[Ics] rated service breaking capacity |
15 kA 75 % conforming to EN 60947-2 – 110 V DC
15 kA 75 % conforming to IEC 60947-2 – 110 V DC 4.5 kA 75 % conforming to EN 60947-2 – 250 V DC 4.5 kA 75 % conforming to IEC 60947-2 – 250 V DC 7.5 kA 75 % conforming to EN 60947-2 – 220 V DC 7.5 kA 75 % conforming to IEC 60947-2 – 220 V DC |
|
[Ui] rated insulation voltage |
500 V DC conforming to IEC 60947-2
500 V DC conforming to EN 60947-2 |
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2 |
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
ON/OFF indication
|
|
mounting mode |
Fixed
|
|
mounting support |
35 mm symmetrical DIN rail
|
|
comb busbar and distribution block compatibility |
Top or bottom: standard
|
|
9 mm pitches |
2
|
|
net weight |
0.128 kg
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
3000 cycles 250 V DC
6000 cycles 250 V DC |
|
provision for padlocking |
Padlockable
|
|
locking options description |
In position O
|
|
tightening torque |
Power circuit: 2.5 N.m top or bottom
|
|
earth-leakage protection |
Without
|
Reviews
There are no reviews yet.