range of product |
Modicon Optimized
|
|
---|---|---|
product or component type |
Safety and isolation transformer
|
|
rated power in VA |
1000 VA
|
|
input voltage |
230 V AC single phase, terminal(s): N-L1
400 V AC phase to phase, terminal(s): L1-L2 |
|
output voltage |
24 V AC
|
|
secondary winding |
Single
|
|
protective cover |
Without
|
|
ambient air temperature for operation |
-20…50 °C
|
input voltage limits |
207…253 V
360…440 V |
|
---|---|---|
network frequency limits |
47…63 Hz
|
|
input voltage tolerance |
+/- 15 V
|
|
efficiency |
94 %
|
|
power dissipation in W |
63.8 W
|
|
output sustained overvoltage |
3 % (no load, hot state)
|
|
maximum voltage drop at rated load |
0.3 %
|
|
no load losses |
26.5 W
|
|
short-circuit voltage |
0,0293
|
|
output protection type |
Against overload, protection technology: external
Against overvoltage, protection technology: external Against short-circuits, protection technology: external |
|
connections – terminals |
For input connection: screw type terminals, connection capacity: 5 x 4 mm² AWG 11
For input ground connection: screw type terminals, connection capacity: 1 x 4 mm² AWG 11 For output connection: screw type terminals, connection capacity: 2 x 10 mm² AWG 6 |
|
marking |
CE
|
|
fixing mode |
By 4 screws diameter: 7 mm on vertical panel, operating position: horizontal
By 4 screws diameter: 7 mm on vertical panel, operating position: vertical By 4 screws diameter: 7 mm on horizontal panel with derating to 90 % |
|
operating altitude |
3000 m
|
|
electrical insulation class |
Class B
|
|
width |
174 mm
|
|
height |
180 mm
|
|
depth |
146 mm
|
|
net weight |
14.3 kg
|