range of product |
Altivar Machine ATV340
|
|
---|---|---|
product or component type |
Variable speed drive
|
|
product specific application |
Machine
|
|
variant |
Standard version
|
|
mounting mode |
Wall mount
|
|
communication port protocol |
Modbus TCP
Modbus serial Ethernet/IP |
|
option card |
Communication module, Profibus DP V1
Communication module, Profinet Communication module, DeviceNet Communication module, CANopen Communication module, EtherCAT |
|
network number of phases |
3 phases
|
|
supply frequency |
50…60 Hz +/- 5 %
|
|
[Us] rated supply voltage |
380…480 V – 15…10 %
|
|
nominal output current |
74.5 A
|
|
motor power kW |
45 kW for normal duty
37 kW for heavy duty |
|
motor power hp |
60 hp for normal duty
50 hp for heavy duty |
|
EMC filter |
Class C3 EMC filter integrated
|
|
IP degree of protection |
IP20
|
|
degree of protection |
UL type 1
|
discrete input number |
8
|
|
---|---|---|
discrete input type |
PTI safe torque off: 0…30 kHz, 24 V DC (30 V)
DI1…DI5 programmable as pulse input, 24 V DC (30 V), impedance: 3.5 kOhm programmable |
|
number of preset speeds |
16 preset speeds
|
|
discrete output number |
1.0
|
|
discrete output type |
Programmable output DQ1, DQ2 30 V DC 100 mA
|
|
analogue input number |
3
|
|
analogue input type |
AI1 software-configurable current: 0…20 mA, impedance: 250 Ohm, resolution 12 bits
AI1 software-configurable temperature probe or water level sensor AI1 software-configurable voltage: 0…10 V DC, impedance: 31.5 kOhm, resolution 12 bits AI2 software-configurable voltage: – 10…10 V DC, impedance: 31.5 kOhm, resolution 12 bits |
|
analogue output number |
2
|
|
analogue output type |
Software-configurable voltage AQ1, AQ2: 0…10 V DC impedance 470 Ohm, resolution 10 bits
Software-configurable current AQ1, AQ2: 0…20 mA impedance 500 Ohm, resolution 10 bits |
|
relay output number |
3
|
|
output voltage |
<= power supply voltage
|
|
relay output type |
Relay outputs R1A
Relay outputs R1C electrical durability 100000 cycles Relay outputs R2A Relay outputs R2C electrical durability 100000 cycles |
|
maximum switching current |
Relay output R1C on resistive load, cos phi = 1: 3 A at 250 V AC
Relay output R1C on resistive load, cos phi = 1: 3 A at 30 V DC Relay output R1C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC Relay output R1C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC Relay output R2C on resistive load, cos phi = 1: 5 A at 250 V AC Relay output R2C on resistive load, cos phi = 1: 5 A at 30 V DC Relay output R2C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC Relay output R2C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC |
|
minimum switching current |
Relay output R1B: 5 mA at 24 V DC
Relay output R2C: 5 mA at 24 V DC |
|
physical interface |
2-wire RS 485
|
|
connector type |
3 RJ45
|
|
method of access |
Slave Modbus RTU
Slave Modbus TCP |
|
transmission rate |
4.8 kbit/s
9.6 kbit/s 19.2 kbit/s 38.4 kbit/s |
|
transmission frame |
RTU
|
|
number of addresses |
1…247
|
|
data format |
8 bits, configurable odd, even or no parity
|
|
type of polarization |
No impedance
|
|
4 quadrant operation possible |
True
|
|
asynchronous motor control profile |
Optimized torque mode
Variable torque standard Constant torque standard |
|
synchronous motor control profile |
Reluctance motor
Permanent magnet motor |
|
pollution degree |
2 conforming to EN/IEC 61800-5-1
|
|
maximum output frequency |
0.599 kHz
|
|
acceleration and deceleration ramps |
Linear adjustable separately from 0.01…9999 s
S, U or customized |
|
motor slip compensation |
Adjustable
Can be suppressed Automatic whatever the load Not available in permanent magnet motor law |
|
switching frequency |
2…16 kHz adjustable
4…16 kHz with derating factor |
|
nominal switching frequency |
4 kHz
|
|
braking to standstill |
By DC injection
|
|
brake chopper integrated |
True
|
|
line current |
79.8 A at 380 V (normal duty)
69.1 A at 480 V (normal duty) 67.1 A at 380 V (heavy duty) 59.0 A at 480 V (heavy duty) |
|
line current |
79.8 A at 380 V with internal line choke (normal duty)
69.1 A at 480 V with internal line choke (normal duty) 67.1 A at 380 V with internal line choke (heavy duty) 59 A at 480 V with internal line choke (heavy duty) 67.1 A 59.0 A |
|
maximum input current |
79.8 A
|
|
maximum output voltage |
480 V
|
|
apparent power |
57.4 kVA at 480 V (normal duty)
49.1 kVA at 480 V (heavy duty) |
|
maximum transient current |
105.6 A during 60 s (normal duty)
105.6 A during 2 s (normal duty) 111.8 A during 60 s (heavy duty) 111.8 A during 2 s (heavy duty) |
|
electrical connection |
Screw terminal, clamping capacity: 0.75…1.5 mm² for control
Screw terminal, clamping capacity: 35…50 mm² for line side Screw terminal, clamping capacity: 35…50 mm² for DC bus Screw terminal, clamping capacity: 50 mm² for motor |
|
prospective line Isc |
50 kA
|
|
base load current at high overload |
74.5 A
|
|
base load current at low overload |
88.0 A
|
|
power dissipation in W |
Natural convection: 90 W at 380 V, switching frequency 4 kHz (heavy duty)
Forced convection: 796 W at 380 V, switching frequency 4 kHz (heavy duty) Natural convection: 105 W at 380 V, switching frequency 4 kHz (normal duty) Forced convection: 943 W at 380 V, switching frequency 4 kHz (normal duty) |
|
electrical connection |
Control: screw terminal0.75…1.5 mm²/AWG 18…AWG 16
Line side: screw terminal35…50 mm²/AWG 2…AWG 1 DC bus: screw terminal35…50 mm²/AWG 3…AWG 1 Motor: screw terminal50 mm²/AWG 1 |
|
with safety function Safely Limited Speed (SLS) |
True
|
|
with safety function Safe brake management (SBC/SBT) |
True
|
|
with safety function Safe Operating Stop (SOS) |
False
|
|
with safety function Safe Position (SP) |
False
|
|
with safety function Safe programmable logic |
False
|
|
with safety function Safe Speed Monitor (SSM) |
False
|
|
with safety function Safe Stop 1 (SS1) |
True
|
|
with sft fct Safe Stop 2 (SS2) |
False
|
|
with safety function Safe torque off (STO) |
True
|
|
with safety function Safely Limited Position (SLP) |
False
|
|
with safety function Safe Direction (SDI) |
False
|
|
protection type |
Thermal protection: motor
Safe torque off: motor Motor phase loss: motor Thermal protection: drive Safe torque off: drive Overheating: drive Overcurrent: drive Output overcurrent between motor phase and earth: drive Output overcurrent between motor phases: drive Short-circuit between motor phase and earth: drive Short-circuit between motor phases: drive Motor phase loss: drive DC Bus overvoltage: drive Line supply overvoltage: drive Line supply undervoltage: drive Input supply loss: drive Exceeding limit speed: drive Break on the control circuit: drive |
|
width |
213.0 mm
|
|
height |
660.0 mm
|
|
depth |
262.0 mm
|
|
net weight |
28.4 kg
|
|
continuous output current |
88 A at 4 kHz for normal duty
74.5 A at 4 kHz for heavy duty |
Reviews
There are no reviews yet.