provided equipment |
Dust filter
Installation guide |
|
---|---|---|
UPS size |
WS
|
colour |
White (RAL 9003)
|
|
---|---|---|
depth |
96.9 cm
|
|
height |
140 cm
|
|
net weight |
584 kg
|
|
USB compatible |
Yes
|
|
width |
50 cm
|
network frequency |
45…65 Hz
|
|
---|---|---|
input voltage limits |
304…477 V
|
|
inputvolt_other |
380 V
415 V |
|
maximum input current |
55 A
|
|
input harmonic distortion |
Less than 3 % for full load
|
|
input voltage |
400 V 3 phases
|
|
load power factor |
0.9 leading to 0.9 lagging
|
|
cos phi |
0.99
|
rated power in W |
30000 W
|
|
---|---|---|
Maximum configurable power in W |
30000 W
|
|
harmonic distortion |
Less than 3 %
|
|
output frequency |
50 Hz sync to mains
60 Hz sync to mains |
|
outputvolt_other |
380 V
415 V |
|
UPS type |
Double conversion online
|
|
output voltage tolerance |
+/- 1.5 %
|
|
output harmonic distortion |
< 3% linear load
|
|
curve equation |
Efficiency
|
|
curve fixed loss |
0.0057
|
|
curve load maximum |
100 %
|
|
curve load minimum |
1 %
|
|
curve proportional loss |
0.0209
|
|
curve square loss |
0.0256
|
|
curve X-axis maximum |
100 %
|
|
curve test cond ID |
Curve fit to measured efficiency data. All measurements taken in normal operating mode, at typical environmental conditions, with 400V 50Hz input and 400V 50Hz balanced resistive load (PF = 1.0) output.
|
|
curve X-axis minimum |
0 %
|
|
curve X-axis title |
Load
|
|
curve X-axis units |
Percentage
|
|
curve Y-axis maximum |
100 %
|
|
curve Y-axis minimum |
50 %
|
|
curve Y-axis title |
Efficiency
|
|
curve Y-axis units |
Percentage
|
|
graph display |
1
|
|
output voltage |
400 V 3 phases
|
|
Maximum configurable power in VA |
30000 VA
|
|
rated power in VA |
30000 VA
|
product certifications |
CE
EAC RCM |
|
---|---|---|
standards |
IEC 62040-1-1
IEC 62040-2 IEC 62040-3 IEC 62040-4 ISTA 2B |