| range |
TeSys
|
|
|---|---|---|
| product name |
TeSys GV2
|
|
| device short name |
GV2LE
|
|
| device application |
Motor
|
|
| poles description |
3P
|
|
| network type |
AC
|
|
| utilisation category |
Category A conforming to IEC 60947-2
AC-3 conforming to IEC 60947-4-1 |
|
| network frequency |
50/60 Hz IEC 60947-2
|
|
| breaking capacity |
100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 |
|
| [Ics] rated service short-circuit breaking capacity |
100 % 500 V AC 50/60 Hz IEC 60947-2
100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % 440 V AC 50/60 Hz IEC 60947-2 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 75 % 690 V AC 50/60 Hz IEC 60947-2 |
|
| trip unit technology |
Magnetic
|
|
| magnetic tripping current |
78 A
|
| fixing mode |
35 mm symmetrical DIN rail: clipped
Panel: screwed (with adaptor plate) |
|
|---|---|---|
| operating position |
Any position
|
|
| motor power kW |
2.2 kW 400/415 V AC 50/60 Hz
3 kW at 500 V AC 50/60 Hz 4 kW 690 V AC 50/60 Hz |
|
| control type |
Toggle
|
|
| [Ue] rated operational voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2
|
|
| [Ui] rated insulation voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2
|
|
| [Uimp] rated impulse withstand voltage |
6 kV IEC 60947-2
|
|
| power dissipation per pole |
1.8 W
|
|
| mechanical durability |
100000 cycles
|
|
| electrical durability |
100000 cycles AC-3 415 V
|
|
| maximum operating rate |
40 cyc/h
|
|
| rated duty |
Continuous conforming to IEC 60947-4-1
|
|
| connections – terminals |
screw clamp terminals 2 0.00…0.01 in² (1…6 mm²) solid
screw clamp terminals 2 0.00…0.01 in² (1.5…6 mm²) flexible without cable end screw clamp terminals 2 0.00…0.01 in² (1…4 mm²) flexible with cable end |
|
| tightening torque |
1.7 N.m on screw clamp terminals
|
|
| mechanical robustness |
Shocks 30 Gn IEC 60068-2-27
Vibrations: 5 Gn, 5…150 Hz conforming to IEC 60068-2-6 |
|
| suitability for isolation |
Yes conforming to IEC 60947-1
|
|
| height |
3.50 in (89 mm)
|
|
| Maximum Width |
1.77 in (45 mm)
|
|
| depth |
3.09 in (78.5 mm)
|
|
| Net Weight |
0.73 lb(US) (0.33 kg)
|





Reviews
There are no reviews yet