Main
range of product | HDM3 |
product or component type | Enclosed moulded case circuit breaker |
suitability for isolation | Yes |
trip unit technology | Thermal-magnetic |
device application | Power distribution protection |
voltage release type | Shunt trip release Undervoltage release |
provided equipment | alarm motor mechanism handle terminal extension interphase barriers MN or MX voltage release |
Complementary
poles description | 3P |
[In] rated current | 100.0 A |
frame size | 100AF |
[Ue] rated operational voltage | 400/415 V |
network type | AC |
network frequency | 50…60 Hz |
electrical durability | 4000.0 cycles |
mechanical durability | 20000.0 cycles with maintenance 10000.0 cycles without maintenance |
[Uimp] rated impulse withstand voltage | 8.0 kV |
[Ics] rated service breaking capacity | 18 kA |
rated breaking capacity | 18 kA |
[Ui] rated insulation voltage | 800.0 V |
mounting mode | Fixed front |
clamping connection capacity | 35 mm² |
tightening torque | 9.5…10.5 N.m |
utilisation category | Category A |
provision for padlocking | Handle padlockable in on and off position |
height | 130.0 mm |
width | 75.0 mm |
depth | 68.0 mm |
net weight | 0.78 kg |
Environment
IP degree of protection | IP20 |
pollution degree | 3 |
ambient air temperature for operation | 40.0 °C |
ambient air temperature for storage | -20…70 °C |
dielectric test voltage | 3 kV |
operating altitude | 0…2000 m |
standards | IEC 60947-2 |
product certifications | CE TÜV |