| range |
TeSys
|
|
|---|---|---|
| product name |
TeSys D
|
|
| product or component type |
Contactor
|
|
| device short name |
LC1D
|
|
| contactor application |
Resistive load
|
|
| utilisation category |
AC-1
|
|
| poles description |
4P
|
|
| power pole contact composition |
4 NO
|
|
| [Ue] rated operational voltage |
Power circuit: <= 1000 V AC 25…400 Hz
Power circuit: <= 460 V DC |
|
| [Ie] rated operational current |
200 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
|
|
| control circuit type |
AC at 50/60 Hz
|
|
| [Uc] control circuit voltage |
220 V AC 50/60 Hz
|
|
| [Uimp] rated impulse withstand voltage |
8 kV conforming to IEC 60947
|
|
| overvoltage category |
III
|
|
| [Ith] conventional free air thermal current |
200 A (at 60 °C) for power circuit
|
|
| Irms rated making capacity |
1260 A at 440 V for power circuit conforming to IEC 60947
|
|
| rated breaking capacity |
1100 A at 440 V for power circuit conforming to IEC 60947
|
|
| [Icw] rated short-time withstand current |
250 A 40 °C – 10 min for power circuit
550 A 40 °C – 1 min for power circuit 950 A 40 °C – 10 s for power circuit 1100 A 40 °C – 1 s for power circuit |
|
| associated fuse rating |
250 A gG at <= 690 V coordination type 1 for power circuit
200 A gG at <= 690 V coordination type 2 for power circuit |
|
| average impedance |
0.6 mOhm – Ith 200 A 50 Hz for power circuit
|
|
| [Ui] rated insulation voltage |
Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified Power circuit: 1000 V conforming to IEC 60947-4-1 |
|
| electrical durability |
0.8 Mcycles 200 A AC-1 at Ue <= 440 V
|
|
| power dissipation per pole |
24 W AC-1
|
|
| Front cover |
With
|
|
| mounting support |
Rail
Plate |
|
| standards |
CSA C22.2 No 14
EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 |
|
| product certifications |
CCC
RINA GOST UL CSA LROS (Lloyds register of shipping) BV GL DNV |
|
| connections – terminals |
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1…2.5 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1…2.5 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²solid without cable end Power circuit: connector 1 cable(s) 10…120 mm²flexible without cable end Power circuit: connector 2 cable(s) 10…50 mm²flexible without cable end Power circuit: connector 1 cable(s) 10…120 mm²flexible with cable end Power circuit: connector 2 cable(s) 10…50 mm²flexible with cable end Power circuit: connector 1 cable(s) 10…120 mm²solid without cable end Power circuit: connector 2 cable(s) 10…50 mm²solid without cable end |
|
| tightening torque |
Control circuit: 1.2 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm
Control circuit: 1.2 N.m – on screw clamp terminals – with screwdriver Philips No 2 Power circuit: 12 N.m – on connector hexagonal screw head 4 mm |
|
| operating time |
6…20 ms opening
20…50 ms closing |
|
| safety reliability level |
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
|
| mechanical durability |
8 Mcycles
|
|
| maximum operating rate |
2400 cyc/h 60 °C
|
| coil technology |
Built-in bidirectional peak limiting diode suppressor
|
|
|---|---|---|
| control circuit voltage limits |
0.3…0.5 Uc (-40…70 °C):drop-out AC 50/60 Hz
0.8…1.15 Uc (-40…55 °C):operational AC 50/60 Hz 1…1.15 Uc (55…70 °C):operational AC 50/60 Hz |
|
| inrush power in VA |
280…350 VA 60 Hz cos phi 0.8 (at 20 °C)
280…350 VA 50 Hz cos phi 0.8 (at 20 °C) |
|
| hold-in power consumption in VA |
2…18 VA 60 Hz cos phi 0.3 (at 20 °C)
2…18 VA 50 Hz cos phi 0.3 (at 20 °C) |
|
| heat dissipation |
3…8 W at 50/60 Hz
|
|
| contact compatibility |
M14
|
|
| compatibility code |
LC1D
|