| range |
TeSys
|
|
|---|---|---|
| product name |
TeSys F
|
|
| product or component type |
Contactor
|
|
| device short name |
LC1F
|
|
| contactor application |
Resistive load
|
|
| utilisation category |
AC-1
|
|
| poles description |
4P
|
|
| power pole contact composition |
4 NO
|
|
| [Ue] rated operational voltage |
<= 690 V AC 50/60 Hz
|
|
| [Ie] rated operational current |
250 A (at <40 °C) at <= 440 V AC-1
|
|
| [Uc] control circuit voltage |
220 V AC 40…400 Hz
|
| [Uimp] rated impulse withstand voltage |
8 kV
|
|
|---|---|---|
| overvoltage category |
III
|
|
| [Ith] conventional free air thermal current |
250 A (at 40 °C)
|
|
| rated breaking capacity |
1200 A conforming to IEC 60947-4-1
|
|
| [Icw] rated short-time withstand current |
1200 A 40 °C – 10 s
700 A 40 °C – 30 s 600 A 40 °C – 1 min 450 A 40 °C – 3 min 350 A 40 °C – 10 min |
|
| associated fuse rating |
160 A aM at <= 440 V
250 A gG at <= 440 V |
|
| average impedance |
0.35 mOhm – Ith 250 A 50 Hz
|
|
| [Ui] rated insulation voltage |
1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 group C |
|
| power dissipation per pole |
22 W AC-1
|
|
| mounting support |
Plate
|
|
| standards |
IEC 60947-1
IEC 60947-4-1 EN 60947-4-1 EN 60947-1 JIS C8201-4-1 |
|
| product certifications |
ABS
UL CB RMRoS BV RINA DNV LROS (Lloyds register of shipping) CCC |
|
| connections – terminals |
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end Power circuit: bar 2 cable(s) – busbar cross section: 25 x 3 mm Power circuit: lugs-ring terminals 1 cable(s) 120 mm² Power circuit: connector 1 cable(s) 120 mm² Power circuit: bolted connection |
|
| tightening torque |
Control circuit: 1.2 N.m
Power circuit: 18 N.m |
|
| control circuit voltage limits |
Operational: 0.85…1.1 Uc 40…400 Hz (at 55 °C)
Drop-out: 0.35…0.55 Uc 40…400 Hz (at 55 °C) |
|
| inrush power in VA |
770 VA 40…400 Hz cos phi 0.9 (at 20 °C)
|
|
| hold-in power consumption in VA |
8.1 VA 40…400 Hz cos phi 0.9 (at 20 °C)
|
|
| heat dissipation |
5.9…7.2 W
|
|
| operating time |
35 ms closing (at Uc)
130 ms opening (at Uc) |
|
| mechanical durability |
10 Mcycles
|
|
| maximum operating rate |
2400 cyc/h 55 °C
|
|
| compatibility code |
LC1F
|





Reviews
There are no reviews yet