Sale!

LV430800 Circuit breaker ComPact NSX160H, 70 kA at 415 VAC, MicroLogic 2.2 trip unit 160 A, 4 poles 4d

Original price was: ₦800,000.00.Current price is: ₦733,883.52. 7.5% VAT

Circuit breaker ComPact NSX160H, 70 kA at 415 VAC, MicroLogic 2.2 trip unit 160 A, 4 poles 4d

 

SKU: LV430800 Category:
Main
range
ComPact
product name
ComPact NSX
range of product
ComPact NSX100…250
device short name
NSXm 160H
product or component type
Circuit breaker
device application
Distribution
Number of poles
4P
protected poles description
4t
3t
3t + N/2
neutral position
Left
[In] rated current
160 A at 40 °C
[Ue] rated operational voltage
690 V AC 50/60 Hz
network type
AC
network frequency
50/60 Hz
suitability for isolation
Yes conforming to EN/IEC 60947-2
utilisation category
Category A
[Icu] rated ultimate short-circuit breaking capacity
10 kA at 600 V AC 50/60 Hz conforming to UL 508
85 kA at 240 V AC 50/60 Hz conforming to UL 508
65 kA at 480 V AC 50/60 Hz conforming to UL 508
10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
Performance level
H 70 kA 415 V AC
trip unit name
Micrologic 2.2
trip unit technology
Electronic
trip unit protection functions
LSoI
control type
Toggle
Circuit breaker mounting mode
Fixed
Complementary
[Ui] rated insulation voltage
800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage
8 kV
[Ics] rated service short-circuit breaking capacity
10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
mechanical durability
40000 cycles
electrical durability
7500 cycles at 690 V In
15000 cycles at 690 V In/2
20000 cycles at 440 V In
40000 cycles at 440 V In/2
mounting support
Backplate
upside connection
Front
downside connection
Front
connection pitch
35 mm
protection type
L : for overload protection (long time)
So : for short time short-circuit protection with fixed delay
I : for instantaneous short-circuit protection
trip unit rating
160 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection)
Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range
63…160 A
Long-time protection delay adjustment type tr
Fixed
[tr] long-time protection delay adjustment range
11 s at 7.2 x Ir
16 s at 6 x Ir
400 s at 1.5 x Ir
thermal memory
20 minutes before and after tripping
Short-time protection pick-up adjustment type Isd
Adjustable 9 settings
[Isd] Short-time protection pick-up adjustment range
1.5…10 x Ir
Short-time protection delay adjustment type tsd
Fixed
Instantaneous protection pick-up adjustment type Ii
Fixed
[Ii] instantaneous protection pick-up adjustment range
2400 A
earth-leakage protection
Without
Neutral protection settings
0.5 x Ir (3t + N/2)
1 x Ir (4t)
No protection (3t)
Number of slots for electrical auxiliaries
5 slot(s)
local signalling
Flashing LED (green) for ready to operate
LED 105 % Ir (red) for overload
LED 90 % Ir (orange) for overload
Width (W)
140 mm
Height (H)
161 mm
Depth (D)
86 mm
net weight
2.6 kg

Reviews

There are no reviews yet.

Only logged in customers who have purchased this product may leave a review.