range of product |
Zelio Control
|
|
---|---|---|
product or component type |
Modular measurement and control relays
|
|
relay type |
Multifunction control relay
|
|
product specific application |
For 3-phase supply
|
|
relay name |
RM17TA
|
|
relay monitored parameters |
Asymmetry
Phase sequence Phase failure detection |
|
time delay |
Adjustable 0.1…10 s, +/- 10 % of the full scale value
|
|
switching capacity in VA |
1250 VA
|
|
measurement range |
208…480 V voltage AC
|
reset time |
1500 ms time delay
|
|
---|---|---|
maximum switching voltage |
250 V AC
250 V DC |
|
minimum switching current |
10 mA at 5 V DC
|
|
maximum switching current |
5 A AC
5 A DC |
|
supply voltage limits |
183…528 V AC
|
|
control circuit voltage limits |
– 12 % + 10 % Un
|
|
power consumption in VA |
0…22 VA at 400 V AC 50 Hz
|
|
control circuit frequency |
50…60 Hz +/- 10 %
|
|
output contacts |
1 C/O
|
|
nominal output current |
5 A
|
|
measurement voltage limits |
183…528 V AC
|
|
hysteresis |
2 %
|
|
delay at power up |
650 ms
|
|
maximum measuring cycle |
150 ms measurement cycle as true rms value
|
|
threshold adjustment voltage |
+2…+17 % in the range 480 V AC
2…20 % of Un selected -2…-17 % in the range 220 V AC -2…-12 % in the range 208 V AC |
|
voltage range |
208…480 V phase to phase
|
|
adjustment of asymmetry threshold |
5…15 % of Un selected
|
|
repeat accuracy |
0.5 % for input and measurement circuit
3 % for time delay |
|
measurement error |
< 0.05 %/°C with temperature variation
< 1 % over the whole range with voltage variation |
|
phase failure sensitivity |
0.7 Un
|
|
response time |
< 200 ms (in the event of a fault)
|
|
marking |
CE
|
|
overvoltage category |
III conforming to IEC 60664-1
|
|
insulation resistance |
> 500 MOhm at 500 V DC conforming to IEC 60255-5
> 500 MOhm at 500 V DC conforming to IEC 60664-1 |
|
[Ui] rated insulation voltage |
400 V conforming to IEC 60664-1
|
|
supply frequency |
50/60 Hz +/- 10 %
|
|
operating position |
Any position without derating
|
|
connections – terminals |
Screw terminals, 1 x 0.5…1 x 4 mm² (AWG 20…AWG 11) solid without cable end
Screw terminals, 2 x 0.5…2 x 2.5 mm² (AWG 20…AWG 14) solid without cable end Screw terminals, 1 x 0.2…1 x 2.5 mm² (AWG 24…AWG 12) flexible with cable end Screw terminals, 2 x 0.2…2 x 1.5 mm² (AWG 24…AWG 16) flexible with cable end |
|
tightening torque |
0.6…1 N.m conforming to IEC 60947-1
|
|
housing material |
Self-extinguishing plastic
|
|
local signalling |
LED (green) for power ON
LED (yellow) for relay ON |
|
mounting support |
35 mm symmetrical DIN rail conforming to EN/IEC 60715
|
|
electrical durability |
100000 cycles
|
|
mechanical durability |
30000000 cycles
|
|
operating rate |
<= 360 operations/hour full load
|
|
utilisation category |
AC-12 conforming to IEC 60947-5-1
AC-13 conforming to IEC 60947-5-1 AC-14 conforming to IEC 60947-5-1 AC-15 conforming to IEC 60947-5-1 DC-12 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1 |
|
safety reliability data |
MTTFd = 502.2 years
B10d = 470000 |
|
width |
17.5 mm
|
|
net weight |
0.13 kg
|