range of product |
Zelio Control
|
|
---|---|---|
product or component type |
Modular measurement and control relays
|
|
relay type |
Voltage control relay
|
|
product specific application |
For single-phase and DC supply
|
|
relay name |
RM17UBE
|
|
relay monitored parameters |
Self-powered
Overvoltage and undervoltage detection |
|
time delay |
Adjustable 0.1…10 s, 0 + 10 % on crossing the threshold
|
|
switching capacity in VA |
1250 VA
|
|
minimum switching current |
10 mA at 5 V DC
|
|
maximum switching current |
5 A AC/DC
|
|
power consumption in VA |
0…3 VA AC
|
|
measurement range |
65…260 V voltage AC/DC
|
|
utilisation category |
AC-12 conforming to IEC 60947-5-1
AC-13 conforming to IEC 60947-5-1 AC-14 conforming to IEC 60947-5-1 AC-15 conforming to IEC 60947-5-1 DC-12 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1 DC-14 conforming to IEC 60947-5-1 |
reset time |
1500 ms time delay
|
|
---|---|---|
maximum switching voltage |
250 V AC/DC
|
|
[Us] rated supply voltage |
110…240 V AC/DC 50/60 Hz +/- 10 %
|
|
supply voltage limits |
50…270 V AC/DC
|
|
maximum power consumption in W |
1 W DC
|
|
immunity to microbreaks |
20 ms
|
|
control circuit frequency |
50…60 Hz +/- 10 %
|
|
output contacts |
1 C/O
|
|
nominal output current |
5 A
|
|
maximum measuring cycle |
150 ms measurement cycle as true rms value
|
|
hysteresis |
3 % fixed of threshold setting
|
|
delay at power up |
1000 ms DC
500 ms AC |
|
measurement accuracy |
+/- 10 % of the full scale value
|
|
repeat accuracy |
+/- 0.5 % for input and measurement circuit
+/- 1 % for time delay |
|
measurement error |
< 1 % over the whole range with voltage variation
0.2 %/°C with temperature variation |
|
polarity |
Non reversible polarity on DC supply
|
|
quality labels |
CE
|
|
overvoltage category |
III conforming to IEC 60664-1
|
|
insulation resistance |
> 500 MOhm at 500 V DC conforming to IEC 60255-5
> 500 MOhm at 500 V DC conforming to IEC 60664-1 |
|
[Ui] rated insulation voltage |
250 V conforming to IEC 60664-1
400 V conforming to IEC 60664-1 |
|
operating position |
Any position without derating
|
|
connections – terminals |
Screw terminals, 1 x 0.5…1 x 4 mm² (AWG 20…AWG 11) solid without cable end
Screw terminals, 2 x 0.5…2 x 2.5 mm² (AWG 20…AWG 14) solid without cable end Screw terminals, 1 x 0.2…2 x 2.5 mm² (AWG 24…AWG 12) flexible with cable end Screw terminals, 2 x 0.2…2 x 1.5 mm² (AWG 24…AWG 16) flexible with cable end |
|
tightening torque |
0.6…1 N.m conforming to IEC 60947-1
|
|
housing material |
Self-extinguishing plastic
|
|
local signalling |
LED (green) for power ON
LED (yellow) for relay ON |
|
mounting support |
35 mm symmetrical DIN rail conforming to EN/IEC 60715
|
|
electrical durability |
100000 cycles
|
|
mechanical durability |
30000000 cycles
|
|
operating rate |
<= 360 operations/hour full load
|
|
safety reliability data |
B10d = 470000
MTTFd = 502.2 years |
|
width |
17.5 mm
|
|
net weight |
0.08 kg
|
|
functionality |
Overvoltage and undervoltage detection
|
|
compatibility code |
RM17
|