General Information
-
- Extended Product Type:
- EK1000-40-11 220-230V 50Hz / 240V 60Hz
-
- Product ID:
- SK827044-AL
-
- EAN:
- 7320500194249
-
- Catalog Description:
- EK1000-40-11 220-230V 50Hz / 240V 60Hz Contactor
-
- Long Description:
- A 4-pole Contactor suitable for Distribution and Rail way applications AC and DC switching. Operated with control voltage, versions from 24….690 AC, 50/60 Hz and 24-220 V DC
Categories
- Products » Low Voltage Products and Systems » Control Products » Contactors » Block Contactors
Technical
-
- Number of Main Contacts NO:
- 4
-
- Number of Main Contacts NC:
- 0
-
- Number of Auxiliary Contacts NO:
- 1
-
- Number of Auxiliary Contacts NC:
- 1
-
- Rated Operational Voltage:
- Main Circuit 1000 V
-
- Conventional Free-air Thermal Current (Ith):
- acc. to IEC 60947-4-1, Open Contactors q = 40 °C 1000 A
-
- Rated Operational Current AC-1 (Ie):
- (1000 V) 40 °C 1000 A
(1000 V) 60 °C 800 A
(1000 V) 70 °C 720 A
(690 V) 40 °C 1000
(690 V) 55 °C 800
(690 V) 60 °C 800 A
(690 V) 70 °C 720
-
- Rated Short-time Withstand Current (Icw):
- at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 6400 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 1200 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 3400 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 6800 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 4400 A
-
- Maximum Electrical Switching Frequency:
- (AC-1) 300 cycles per hour
-
- Rated Insulation Voltage (Ui):
- acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
acc. to UL/CSA 600 V
-
- Rated Impulse Withstand Voltage (Uimp):
- 8 kV
-
- Mechanical Durability:
- 5 million
-
- Maximum Mechanical Switching Frequency:
- 3600 cycles per hour
-
- Coil Operating Limits:
- (acc. to IEC 60947-4-1) Uc (at θ ≤ 70 °C)
-
- Rated Control Circuit Voltage (Uc):
- 50 Hz 220 … 230 V
60 Hz 240 V
-
- Coil Consumption:
- Holding at Max. Rated Control Circuit Voltage 50 Hz 125 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 140 V·A
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 3500 V·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 4000 V·A
-
- Operate Time:
- Between Coil De-energization and NC Contact Closing 10 … 20 ms
Between Coil De-energization and NO Contact Opening 13 … 23 ms
Between Coil Energization and NC Contact Opening 25 … 55 ms
Between Coil Energization and NO Contact Closing 30 … 60 ms
-
- Degree of Protection:
- acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
-
- Connecting Terminals (delivered in open position) Main Poles:
- Flat type c/w screws and bolts
-
- Terminal Type:
- Main Circuit: Bars
Reviews