provided equipment |
CD with software
Documentation CD Installation guide Temperature probe USB cable Warranty card Web/SNMP management card |
|
---|---|---|
product web sub-family |
High density
|
|
Number of tare power |
70 W
|
|
Number of power module free slots |
0
|
|
Number of power module filled slots |
0
|
|
redundant |
No
|
|
UPS size |
S
|
colour |
Black
|
|
---|---|---|
depth |
71.5 cm
|
|
height |
43.2 cm
|
|
mounting location |
Front
|
|
mounting preference |
No preference
|
|
net weight |
111.82 kg
|
|
mounting mode |
Rack-mounted with kit
|
|
two post mountable |
0
|
|
USB compatible |
Yes
|
|
width |
26.3 cm
|
network frequency |
40…70 Hz auto-sensing
|
|
---|---|---|
number of input connectors |
1 hard wire 3-wire (1P + N + E)
1 hard wire 5-wire (3P + N + E) |
|
input voltage limits |
100…275 V adjustable (half load)
173…476 V adjustable (half load) 160…275 V |
|
inputvolt_other |
220 V
240 V 380 V 415 V |
|
input voltage |
230 V
400 V 3 phases |
rated power in W |
8000 W
|
|
---|---|---|
Maximum configurable power in W |
8000 W
|
|
harmonic distortion |
Less than 2 %
|
|
output frequency |
50/60 Hz +/- 3 Hz sync to mains
|
|
outputvolt_other |
220 V
240 V |
|
crest factor |
3 : 1
|
|
UPS type |
Double conversion online
|
|
Wave type |
Sine wave
|
|
output connector type |
Hard wire 3-wire (H N + E) 1
|
|
nb of power socket outlets |
6 IEC 60320 C13
3 IEC Jumpers 4 IEC 60320 C19 |
|
bypass type |
Internal bypass (automatic and manual)
|
|
curve equation |
Efficiency
|
|
curve fixed loss |
0.0112
|
|
curve load maximum |
100 %
|
|
curve load minimum |
2 %
|
|
curve proportional loss |
0.0208
|
|
curve square loss |
0.0226
|
|
curve X-axis maximum |
100 %
|
|
curve test cond ID |
Curve fit of data measured in accordance with the ENERGY STAR Test Method for Uninterruptible Power Supplies. All measurements taken in normal mode(s), at typical environmental conditions, with 230V/50Hz electrical input and balanced resistive load (PF = 1.0) output.
|
|
curve X-axis minimum |
0 %
|
|
curve X-axis title |
Load
|
|
curve X-axis units |
Percentage
|
|
curve Y-axis maximum |
100 %
|
|
curve Y-axis minimum |
50 %
|
|
curve Y-axis title |
Efficiency
|
|
curve Y-axis units |
Percentage
|
|
graph display |
1
|
|
output voltage |
230 V
|
|
Maximum configurable power in VA |
8000 VA
|
|
rated power in VA |
8000 VA
|
product certifications |
CE
EAC IRAM RCM VDE |
|
---|---|---|
marking |
CE Mark
|
|
standards |
EN/IEC 62040-1
EN/IEC 62040-2 |