| provided equipment |
Basic UPS signaling RS-232 cable
CD with software User manual USB cable |
|
|---|---|---|
| max runtime |
4 min
|
|
| Number of tare power |
41 W
|
|
| Number of power module free slots |
0
|
|
| Number of power module filled slots |
0
|
|
| redundant |
No
|
|
| UPS size |
WS
|
| cable length |
1.50 m
|
|
|---|---|---|
| colour |
Black
|
|
| depth |
40 cm
|
|
| height |
23.8 cm
|
|
| net weight |
16.8 kg
|
|
| USB compatible |
Yes
|
|
| width |
14.5 cm
|
| network frequency |
40…70 Hz
|
|
|---|---|---|
| plug standard |
IEC 60320 C14
|
|
| input voltage limits |
110…285 V adjustable (half load)
160…280 V |
|
| inputvolt_other |
220 V
240 V |
|
| number of cables |
1
|
|
| input voltage |
230 V
|
| rated power in W |
1600 W
|
|
|---|---|---|
| Maximum configurable power in W |
1600 W
|
|
| output frequency |
50/60 Hz +/- 3 Hz sync to mains
|
|
| outputvolt_other |
220 V
240 V |
|
| crest factor |
3 : 1
|
|
| UPS type |
Double conversion online
|
|
| Wave type |
Sine wave
|
|
| nb of power socket outlets |
4 IEC 60320 C13
|
|
| bypass type |
Internal bypass (automatic and manual)
|
|
| curve equation |
Efficiency
|
|
| curve fixed loss |
0.0285
|
|
| curve load maximum |
100 %
|
|
| curve load minimum |
4 %
|
|
| curve proportional loss |
0.0517
|
|
| curve square loss |
0.0279
|
|
| curve X-axis maximum |
100 %
|
|
| curve test cond ID |
Curve fit of data measured in accordance with the ENERGY STAR Test Method for Uninterruptible Power Supplies. All measurements are taken in normal mode(s), at typical environmental conditions, with 230V/50Hz electrical input and balanced resistive load (PF = 1.0) output.
|
|
| curve X-axis minimum |
0 %
|
|
| curve X-axis title |
Load
|
|
| curve X-axis units |
Percentage
|
|
| curve Y-axis maximum |
100 %
|
|
| curve Y-axis minimum |
50 %
|
|
| curve Y-axis title |
Efficiency
|
|
| curve Y-axis units |
Percentage
|
|
| efficiency |
88 % (full load)
|
|
| graph display |
1
|
|
| half load runtime |
00:12:00 800 W
|
|
| output voltage |
230 V
|
|
| Maximum configurable power in VA |
2000 VA
|
|
| rated power in VA |
2000 VA
|
|
| runtime at 400W |
00:26:00
|
| product certifications |
CE
EAC |
|
|---|---|---|
| standards |
IEC 62040-1-1
IEC 62040-1-2 |