provided equipment |
Basic UPS signaling RS-232 cable
CD with software User manual USB cable |
|
---|---|---|
Number of tare power |
32 W
|
|
Number of power module free slots |
0
|
|
Number of power module filled slots |
0
|
|
redundant |
No
|
|
UPS size |
WS
|
color |
Black
|
|
---|---|---|
depth |
42.5 cm
|
|
height |
33.6 cm
|
|
net weight |
26.8 kg
|
|
USB compatible |
Yes
|
|
width |
19 cm
|
network frequency |
40…70 Hz
|
|
---|---|---|
plug standard |
IEC 60320 C20
|
|
input voltage limits |
160…280 V
|
|
inputvolt_other |
220 V
240 V |
|
number of cables |
1
|
|
input voltage |
230 V
|
rated power in W |
2400 W
|
|
---|---|---|
Maximum configurable power in W |
2400 W
|
|
output frequency |
50/60 Hz +/- 3 Hz sync to mains
|
|
outputvolt_other |
220 V
240 V |
|
crest factor |
3: 1
|
|
UPS type |
Double conversion online
|
|
Wave type |
Sine wave
|
|
nb of power socket outlets |
6 IEC 60320 C13
1 IEC 60320 C19 |
|
bypass type |
Internal bypass (automatic and manual)
|
|
curve equation |
Efficiency
|
|
curve fixed loss |
0.0176
|
|
curve load maximum |
100 %
|
|
curve load minimum |
2 %
|
|
curve proportional loss |
0.0341
|
|
curve square loss |
0.0319
|
|
curve X-axis maximum |
100 %
|
|
curve test cond ID |
Curve fit of data measured in accordance with the ENERGY STAR Test Method for Uninterruptible Power Supplies. All measurements are taken in normal mode(s), at typical environmental conditions, with 230V/50Hz electrical input and balanced resistive load (PF = 1.0) output.
|
|
curve X-axis minimum |
0 %
|
|
curve X-axis title |
Load
|
|
curve X-axis units |
Percentage
|
|
curve Y-axis maximum |
100 %
|
|
curve Y-axis minimum |
50 %
|
|
curve Y-axis title |
Efficiency
|
|
curve Y-axis units |
Percentage
|
|
efficiency |
88 % (full load)
|
|
graph display |
1
|
|
half load runtime |
00:13:00 1200 W
|
|
output voltage |
230 V
|
|
Maximum configurable power in VA |
3000 VA
|
|
rated power in VA |
3000 VA
|
|
runtime at 600W |
00:31:00
|
product certifications |
CE
EAC |
|
---|---|---|
standards |
IEC 62040-1-1