network rated voltage |
400 V AC 50 Hz
415 V AC 50 Hz |
|
---|---|---|
reactive power rating |
125 kvar
|
|
operating mode |
Automatic
|
|
range |
VarSet
|
|
device short name |
VarSet automatic
|
|
product or component type |
Capacitor bank
|
network pollution level |
Low polluted
|
|
---|---|---|
[Gh/Sn] harmonic pollution rate |
15…25 %
|
|
[THDU] total harmonic distorsion of voltage |
3…4 %
|
|
power per step |
25 kvar
|
|
step composition |
25 + 2×50
|
|
location of connection |
Bottom
|
|
controller type |
Varplus Logic VPL6 Modbus
|
|
capacitor technology |
VarplusCan
|
|
poles description |
3P
|
|
capacitance tolerance |
– 5 % to 10 %
|
|
[Ui] rated insulation voltage |
690 V
|
|
[Uimp] rated impulse withstand voltage |
8 kV
|
|
maximum permissible voltage |
1.1 x Un (8 hours over 24 hours) conforming to IEC 60831
|
|
[Imp] maximum permanent current |
Capacitor: 1.8 x In at 480 V conforming to IEC 60831
Battery: 1.43 x In at 400 V conforming to IEC 61439-2 Battery: 1.19 x In at 415 V conforming to IEC 61439-2 |
|
main incomer protection |
Circuit breaker protection
|
|
breaking capacity |
Icu 50 kA
|
|
control type |
Rotary handle
|
|
step protection type |
Overload: harmonic control from VarPlus Logic
Short-circuit: main circuit breaker |
|
accessibility for operation |
Front
|
|
colour |
Grey (RAL 7035)
|
|
maximum weight |
131 kg
|
|
height |
1200 mm
|
|
width |
800 mm
|
|
depth |
300 mm
|
|
provided equipment |
Auxiliary transformer
|
|
internal voltage transformer |
400/230 V – 250 VA
|
|
function available |
Alarm contact
GenSet shedding contact |
Reviews