range |
EasyLogic
|
|
---|---|---|
product name |
EasyLogic DM6X00H NC
|
|
device short name |
DM6000H
|
|
product or component type |
VAF PF meter
|
device application |
Remote monitoring
|
|
---|---|---|
type of measurement |
Current
Voltage Frequency RPM |
|
metering type |
Unbalance current
Calculated neutral current Unbalance voltage Rotation speed Phase currents Voltage U21, U32, U13, V1, V2, V3 Frequency Average voltage Vavg Average current Iavg |
|
counter functions |
Power interruption
ON hour counting |
|
[Us] rated supply voltage |
48…277 V AC 45…65 Hz
48…277 V DC |
|
network frequency |
50 Hz
60 Hz |
|
[In] rated current |
1 A
5 A |
|
type of network |
2P + N
2P 3P + N 3P 1P + N |
|
maximum power consumption in VA |
4 VA at 240 V between phase and neutral
|
|
maximum power consumption in W |
2 W at 240 V
|
|
display type |
8 segments LED
|
|
display colour |
Red
|
|
messages display capacity |
3 fields of 4 characters
|
|
display digits |
12 digit(s) – 14.2 mm in height
|
|
communication of data |
Reading of measurements
Instantaneous and demand values Revolution speed All counters |
|
tamperproof of settings |
Protected by access code
|
|
sampling rate |
32 samples/cycle
|
|
measurement current |
5…6000 mA
|
|
Signal |
Current 0.005…10 A (impedance 0.3 MOhm)6 x
|
|
measurement voltage |
35…480 V AC 50…60 Hz between phases
46…277 V AC 50…60 Hz between phase and neutral 277…999000 V AC 50…60 Hz with external VT |
|
frequency measurement range |
45…65 Hz
|
|
measurement accuracy |
Frequency +/- 0.05 %
Power factor +/- 0.01 Current +/- 1 % Voltage +/- 1 % |
|
accuracy class |
Class 1
|
|
Demand intervals |
1 s
|
|
local signalling |
Green LED: activity
Red LED: output signal 1…9999000 pulse/ k_h (kWh, kVAh, kVARh) |
|
communication port protocol |
–
|
|
material |
Polycarbonate
|
|
flame retardance |
V-0 conforming to UL 94
|
|
mounting mode |
Flush-mounted
|
|
mounting support |
Framework
|
|
installation category |
III
|
|
type of installation |
Indoor installation
|
|
measurement category |
Category III 480 V
|
|
electrical insulation class |
Class II
|
|
connections – terminals |
Current circuit: screw clamp terminals (bottom) 2.08…3.31 mm² cable(s)
Voltage circuit: screw clamp terminals (top) 0.82…3.31 mm² cable(s) Control circuit: screw clamp terminals (top) 0.82…3.31 mm² cable(s) |
|
tightening torque |
Current circuit: 0.9…1 N.m Philips No 2 screwdriver
Voltage circuit: 0.9…1 N.m Philips No 2 screwdriver Control circuit: 0.9…1 N.m Philips No 2 screwdriver |
|
wire stripping length |
Current circuit: 3.68 mm
Voltage circuit: 7 mm Control circuit: 7 mm |
|
standards |
IEC 61010-1:ed. 3
UL 61010-1:ed. 3 |
|
product certifications |
CE conforming to IEC 61010-1
CULus conforming to UL 61010-1 CULus conforming to CSA C22.2 No 61010-1 C-Tick |
|
width |
96 mm
|
|
depth |
13 mm outside:
49 mm panel: |
|
height |
96 mm
|
|
net weight |
300 g
|
Reviews