range |
TeSys
|
|
---|---|---|
product name |
TeSys VARIO
|
|
device short name |
V
|
|
product or component type |
Switch body
|
|
performance level |
High performance
|
|
poles description |
3P
|
|
contacts type and composition |
3 NO
|
|
network type |
AC
DC |
|
network frequency |
50/60 Hz
|
|
suitability for isolation |
Yes
|
mounting support |
Symmetrical rail
Plate |
|
---|---|---|
[Ue] rated operational voltage |
690 V AC 50/60 Hz
|
|
[Uimp] rated impulse withstand voltage |
8 kV
|
|
[Ith] conventional free air thermal current |
125 A
|
|
[Ithe] conventional enclosed thermal current |
100 A
|
|
[Ie] rated operational current |
68.5 A AC-23 Ue: 400 V
|
|
rated operational power in W |
22 kW at 230…240 V (AC-3)
30 kW at 400…415 V (AC-3) 30 kW at 690 V (AC-3) 37 kW at 500 V (AC-3) 37 kW at 690 V (AC-23A) 45 kW at 500 V (AC-23A) 22 kW at 230…240 V (AC-23A) 37 kW at 400…415 V (AC-23A) |
|
intermittent duty class |
30
|
|
Making capacity ( I Rms) |
1250 A at 400 V AC-21A
1250 A at 400 V AC-22A 1250 A at 400 V AC-23A |
|
[Icm] rated short-circuit making capacity |
2.8 kA at 400 V at Ipeak
|
|
[Icw] rated short-time withstand Rms current |
1500 A at 400 V duration: 1 s
|
|
rated conditional short-circuit current |
10 kA at 400 V – associated fuse 125 A aM
10 kA at 400 V – associated fuse 125 A gG |
|
breaking capacity |
1000 A at 400 V (AC-21A)
1000 A at 400 V (AC-22A) 1000 A at 400 V (AC-23A) |
|
mechanical durability |
30000 cycles
|
|
electrical durability |
30000 cycles AC-21
30000 cycles DC-1…5 |
|
connections – terminals |
Power circuit: screw clamp terminals70 mm² – flexible – with cable end
Power circuit: screw clamp terminals95 mm² – solid |
|
tightening torque |
Power circuit: 22.6 N.m – on screw clamp terminals
|
|
height |
125 mm
|
|
width |
90 mm
|
|
depth |
90 mm
|
|
net weight |
0.9 kg
|