| range |
TeSys
|
|
|---|---|---|
| product name |
TeSys VARIO
|
|
| device short name |
V
|
|
| product or component type |
Switch body
|
|
| performance level |
High performance
|
|
| poles description |
3P
|
|
| contacts type and composition |
3 NO
|
|
| network type |
DC
AC |
|
| network frequency |
50/60 Hz
|
|
| suitability for isolation |
Yes
|
| mounting support |
Plate
Symmetrical rail |
|
|---|---|---|
| [Ue] rated operational voltage |
690 V AC 50/60 Hz
|
|
| [Uimp] rated impulse withstand voltage |
8 kV
|
|
| [Ith] conventional free air thermal current |
80 A
|
|
| [Ithe] conventional enclosed thermal current |
63 A
|
|
| [Ie] rated operational current |
57 A AC-23 Ue: 400 V
|
|
| rated operational power in W |
15 kW at 230…240 V (AC-3)
22 kW at 400…415 V (AC-3) 30 kW at 500 V (AC-3) 30 kW at 690 V (AC-23A) 37 kW at 500 V (AC-23A) 18.5 kW at 690 V (AC-3) 18.5 kW at 230…240 V (AC-23A) 30 kW at 400…415 V (AC-23A) |
|
| intermittent duty class |
30
|
|
| Making capacity ( I Rms) |
800 A at 400 V AC-21A
800 A at 400 V AC-22A 800 A at 400 V AC-23A |
|
| [Icm] rated short-circuit making capacity |
2.1 kA at 400 V at Ipeak
|
|
| [Icw] rated short-time withstand Rms current |
960 A at 400 V duration: 1 s
|
|
| rated conditional short-circuit current |
10 kA at 400 V – associated fuse 80 A aM
10 kA at 400 V – associated fuse 80 A gG |
|
| breaking capacity |
640 A at 400 V (AC-21A)
640 A at 400 V (AC-22A) 640 A at 400 V (AC-23A) |
|
| mechanical durability |
30000 cycles
|
|
| electrical durability |
30000 cycles AC-21
30000 cycles DC-1…5 |
|
| connections – terminals |
Power circuit: screw clamp terminals16 mm² – flexible – with cable end
Power circuit: screw clamp terminals25 mm² – solid |
|
| tightening torque |
Power circuit: 4 N.m – on screw clamp terminals
|
|
| height |
83 mm
|
|
| width |
60 mm
|
|
| depth |
65 mm
|
|
| net weight |





Reviews