AX50-30-11-80 220-230V50Hz/230-240V60Hz Contactor

SKU: 1SBL351074R8011 Category:

General Information

  • Extended Product Type:
    AX50-30-11-80
  • Product ID:
    1SBL351074R8011
  • EAN:
    3471522404800
  • Catalog Description:
    AX50-30-11-80 220-230V50Hz/230-240V60Hz Contactor
  • Long Description:
    AX50…AX80 contactors are mainly used for controlling 3-phase motors and power circuits up to 690 V AC. These contactors are of the block type design with: – 3 main poles – control circuit: AC operated – add-on auxiliary contact blocks (optional) for side mounting and a wide range of accessories.

Categories

  • Products » Low Voltage Products and Systems » Control Products » Contactors » Block Contactors

Technical

  • Number of Main Contacts NO:
    3
  • Number of Main Contacts NC:
    0
  • Number of Auxiliary Contacts NO:
    1
  • Number of Auxiliary Contacts NC:
    1
  • Rated Operational Voltage:
    Auxiliary Circuit 690 V
    Main Circuit 690 V
  • Rated Frequency (f):
    Auxiliary Circuit 50 / 60 Hz
    Main Circuit 50 / 60 Hz
  • Conventional Free-air Thermal Current (Ith):
    acc. to IEC 60947-4-1, Open Contactors q = 40 °C 100 A
  • Rated Operational Current AC-1 (Ie):
    (690 V) 40 °C 100 A
    (690 V) 70 °C 70 A
    (220 / 240 V) 55 °C 85 A
  • Rated Operational Current AC-3 (Ie):
    (220 / 230 / 240 V) 55 °C 53 A
    (380 / 400 V) 55 °C 50 A
    (415 V) 55 °C 50 A
    (440 V) 55 °C 45 A
    (500 V) 55 °C 45 A
    (690 V) 55 °C 35 A
  • Rated Operational Power AC-3 (Pe):
    (220 / 230 / 240 V) 15 kW
    (380 / 400 V) 22 kW
    (415 V) 25 kW
    (440 V) 25 kW
    (500 V) 30 kW
    (690 V) 30 kW
  • Rated Short-time Withstand Current (Icw):
    at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 650 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 370 A
    for 1 s -empty- A
  • Maximum Breaking Capacity:
    cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1300 A
    cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 630 A
  • Maximum Electrical Switching Frequency:
    (AC-1) 600 cycles per hour
    (AC-3) 600 cycles per hour
  • Rated Insulation Voltage (Ui):
    acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
  • Rated Impulse Withstand Voltage (Uimp):
    6 kV
  • Maximum Mechanical Switching Frequency:
    3600 cycles per hour
  • Rated Control Circuit Voltage (Uc):
    50 Hz 220 … 230 V
    60 Hz 230 … 240 V
  • Operate Time:
    Between Coil De-energization and NC Contact Closing 7 … 14 ms
    Between Coil De-energization and NO Contact Opening 4 … 11 ms
    Between Coil Energization and NC Contact Opening 7 … 22 ms
    Between Coil Energization and NO Contact Closing 8 … 27 ms
  • Degree of Protection:
    acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
    acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
  • Terminal Type:
    Screw Terminals

Technical UL/CSA

  • General Use Rating UL/CSA:
    (600 V AC) 80 A
  • Horsepower Rating UL/CSA:
    (120 V AC) Single Phase 3 Hp
    (240 V AC) Single Phase 10 Hp
    (200 … 208 V AC) Three Phase 15 Hp
    (220 … 240 V AC) Three Phase 20 Hp
    (440 … 480 V AC) Three Phase 40 Hp
    (550 … 600 V AC) Three Phase 50 Hp
  • Tightening Torque UL/CSA:
    Auxiliary Circuit 9 in·lb
    Control Circuit 9 in·lb
    Main Circuit 35 in·lb