range |
Vigirex
|
|
---|---|---|
range of product |
Vigirex
|
|
device short name |
RH10M
|
|
product or component type |
Residual current protection relay
|
|
Current sensors compatibility |
TOA earth leakage current sensor
A earth leakage current sensor L earth leakage current sensor |
|
relay application |
Residual current protection relay
|
Monitored distribution system |
1000 V – AC at 50/60 Hz (maximum)
1000 V – AC at 400 Hz (maximum) |
|
---|---|---|
earthing system |
IT
TN-S TT |
|
[Us] rated supply voltage |
380…415 V AC 50/60 Hz
|
|
power consumption in VA |
4 VA
|
|
type of measurement |
Earth fault current internal measurement, range: 80…100 %
|
|
residual earth-leakage time delay adjustment type |
Instantaneous 0.03 A
|
|
test function |
Remote test
Local |
|
monitoring |
Electronics (continuous)
Power supply (continuous) Relay/sensor link (continuous) |
|
[Ithe] conventional enclosed thermal current |
8 A
|
|
minimum load |
10 mA at 12 V
|
|
net weight |
0.3 kg
|
|
IP degree of protection |
IP40 on front face: conforming to EN/IEC 60529
IP30 on side parts: conforming to EN/IEC 60529 IP20 on connection terminals: conforming to EN/IEC 60529 |
|
IK degree of protection |
IK07 conforming to EN 50102
|
|
mechanical robustness |
Fire resistance conforming to IEC 60695-2-1
IK protection 2 joules: IK07 conforming to EN 50102 Vibrations 13.2…100 Hz: 0.7 g Vibrations 2…13.2 Hz: +/- 1 mm |
|
earth-leakage protection class |
Class A
Class AC |
|
overvoltage category |
IV
|
|
tamperproof of settings |
Protected by sealable cover
|
|
mounting support |
DIN rail
|
|
height |
81 mm
|
|
width |
54 mm
|
|
depth |
74 mm
|
|
9 mm pitches |
6
|
|
connections – terminals |
Auxiliary power supply: terminal block cable(s) 0.2…2.5 mm² flexible AWG 24…AWG 12
Auxiliary power supply: terminal block cable(s) 0.2…2.5 mm² rigid AWG 24…AWG 12 Auxiliary power supply: terminal block cable(s) 0.25…2.5 mm² flexible AWG 24…AWG 12 Fault: screw terminal cable(s) 0.2…2.5 mm² flexible AWG 24…AWG 12 Fault: screw terminal cable(s) 0.2…4 mm² rigid AWG 24…AWG 12 Fault: screw terminal cable(s) 0.25…2.5 mm² flexible AWG 24…AWG 12 Relay test and fault reset: screw terminal cable(s) 0.14…1 mm² flexible AWG 26…AWG 16 Relay test and fault reset: screw terminal cable(s) 0.14…1.5 mm² rigid AWG 26…AWG 16 Relay test and fault reset: screw terminal cable(s) 0.25…0.5 mm² flexible AWG 26…AWG 16 Sensor: screw terminal cable(s) 0.14…1 mm² flexible AWG 26…AWG 16 Sensor: screw terminal cable(s) 0.14…1.5 mm² rigid AWG 26…AWG 16 Sensor: screw terminal cable(s) 0.25…0.5 mm² flexible AWG 26…AWG 16 Voltage presence: screw terminal cable(s) 0.2…2.5 mm² flexible AWG 24…AWG 12 Voltage presence: screw terminal cable(s) 0.2…4 mm² rigid AWG 24…AWG 12 Voltage presence: screw terminal cable(s) 0.25…2.5 mm² flexible AWG 24…AWG 12 |
|
wire stripping length |
Auxiliary power supply: 7 mm for top connection
Fault: 8 mm for bottom connection Relay test and fault reset: 5 mm for bottom connection Sensor: 5 mm for top connection Voltage presence: 8 mm for bottom connection |
|
tightening torque |
Auxiliary power supply: 0.6 N.m top
Fault: 0.6 N.m bottom Relay test and fault reset: 0.25 N.m bottom Sensor: 0.25 N.m top Voltage presence: 0.6 N.m bottom |
Reviews
There are no reviews yet.