| range of product |
C120
|
|
|---|---|---|
| range |
Acti 9
|
|
| product name |
C120
|
|
| product or component type |
Miniature circuit-breaker
|
|
| device short name |
C120H
|
|
| device application |
Distribution
|
|
| poles description |
4P
|
|
| number of protected poles |
4
|
|
| [In] rated current |
63 A at 30 °C
|
|
| network type |
AC
|
|
| trip unit technology |
Thermal-magnetic
|
|
| curve code |
C
|
|
| breaking capacity |
15000Â A Icn at 230…400 V AC 50/60 Hz conforming to EN/IEC 60898-1
10Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 30Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15Â kA Icu at <= 500 V DC conforming to EN/IEC 60947-2 |
|
| suitability for isolation |
Yes conforming to IEC 60947-2
|
| network frequency |
50/60 Hz
|
|
|---|---|---|
| [Ue] rated operational voltage |
380…415 V AC 50/60 Hz
<= 500 V DC 220…240 V AC 50/60 Hz 440 V AC 50/60 Hz 230…400 V AC 50/60 Hz |
|
| magnetic tripping limit |
5…10 x In
|
|
| [Ics] rated service breaking capacity |
7500Â A 50Â % conforming to EN/IEC 60898-1 – 230…400 V AC 50/60 Hz
5Â kA 50Â % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz 15Â kA 50Â % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz 7.5Â kA 50Â % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz 15Â kA 100Â % conforming to EN/IEC 60947-2 – <= 500 V DC |
|
| limitation class |
3 conforming to EN/IEC 60947-2
|
|
| [Ui] rated insulation voltage |
500Â V AC 50/60 Hz conforming to EN/IEC 60947-2
|
|
| [Uimp] rated impulse withstand voltage |
6Â kV conforming to EN/IEC 60947-2
|
|
| contact position indicator |
Yes
|
|
| control type |
Toggle
|
|
| local signalling |
ON/OFF indication
|
|
| mounting mode |
Clip-on
|
|
| mounting support |
35 mm symmetrical DIN rail
|
|
| comb busbar and distribution block compatibility |
YES
|
|
| 9 mm pitches |
12
|
|
| height |
81Â mm
|
|
| width |
108Â mm
|
|
| depth |
73Â mm
|
|
| net weight |
0.82Â kg
|
|
| colour |
White
|
|
| mechanical durability |
20000Â cycles
|
|
| electrical durability |
10000Â cycles conforming to IEC 60947-2
|
|
| connections – terminals |
Tunnel type terminals1…50 mm² rigid
Tunnel type terminals1.5…35 mm² flexible |
|
| wire stripping length |
15Â mm
|
|
| tightening torque |
3.5Â N.m
|
|
| earth-leakage protection |
Separate block
|





Reviews