ATS48C79Y Soft starter for asynchronous motor – ATS48 – 720 A – 208..690 V – 220..710 KW

4,500,070.00 7.5% VAT

Soft starter for asynchronous motor – ATS48 – 720 A – 208..690 V – 220..710 KW

SKU: ATS48C79Y Category:
Main
range of product
Altistart 48
product or component type
Soft starter
product destination
Asynchronous motors
product specific application
Heavy duty industry and pumps
device short name
ATS48
power supply voltage
208…690 V – 15…10 %
motor power kW
220 kW 230 V for standard applications
355 kW 400 V for severe applications
400 kW 400 V for standard applications
400 kW 440 V for severe applications
500 kW 440 V for standard applications
500 kW 500 V for standard applications
500 kW 525 V for standard applications
630 kW 660 V for severe applications
630 kW 690 V for severe applications
710 kW 660 V for standard applications
710 kW 690 V for standard applications
Maximum Horse Power Rating
200 hp 208 V for severe applications
250 hp 208 V for standard applications
250 hp 230 V for severe applications
300 hp 230 V for standard applications
500 hp 460 V for severe applications
600 hp 460 V for standard applications
600 hp 575 V for severe applications
800 hp 575 V for standard applications
power dissipation in W
2073 W for standard applications
2537 W for standard applications
utilisation category
AC-53A
type of start
Start with torque control (current limited to 5 In)
Icl nominal current
790 A connection in the motor supply line for standard applications
790 A connection in the motor supply line for severe applications
IP degree of protection
IP00
Complementary
assembly style
With heat sink
function available
External bypass (optional)
power supply voltage limits
177…759 V
power supply frequency
50…60 Hz – 5…5 %
power supply frequency limits
47.5…63 Hz
device connection
In the motor supply line
factory setting current
720 A
[Uc] control circuit voltage
110 – 15 % to 230 + 10 %, 50/60 Hz
control circuit consumption
80 W
discrete output number
2
discrete output type
LO1) logic output 0 V common configurable
LO2) logic output 0 V common configurable
R1) relay outputs fault relay NO
R2) relay outputs end of starting relay NO
R3) relay outputs motor powered NO
output absolute accuracy precision
+/- 5 %
minimum switching current
10 mA 6 V DC relay outputs
maximum switching current
Logic output 0.2 A 30 V DC
Relay outputs 1.8 A 230 V AC inductive, cos phi = 0.5 20 ms
Relay outputs 1.8 A 30 V DC inductive, cos phi = 0.5 20 ms
discrete input number
5
discrete input type
PTC, 750 Ohm 77 °F (25 °C)
Stop, Run, LI3, LI4) logic, <= 8 mA 4300 Ohm
discrete input voltage
24 V <= 30 V
discrete input logic
Positive logic Stop, Run, LI3, LI4 < 5 V <= 2 mA > 11 V, >= 5 mA
starting current
0.4…1.3 Icl adjustable
analogue output type
Current output AO 0-20 mA or 4-20 mA 500 Ohm
communication port protocol
Modbus
connector type
1 RJ45
communication data link
Serial
physical interface
RS485 multidrop
transmission rate
4800, 9600 or 19200 bps
max nodes number
31
protection type
Phase failure line
Thermal protection motor
Thermal protection starter
marking
CE
type of cooling
Forced convection
operating position
Vertical +/- 10 degree
height
35.04 in (890 mm)
width
30.31 in (770 mm)
depth
12.40 in (315 mm)
Net Weight
253.53 lb(US) (115 kg)
Motor power range AC-3
110…220 kW 200…240 V 3 phase
250…500 kW at 380…440 V 3 phases
250…500 kW 480…500 V 3 phase
motor starter type
Soft starter

Reviews

There are no reviews yet.