range of product |
Altivar 212
|
|
---|---|---|
product or component type |
Variable speed drive
|
|
device short name |
ATV212
|
|
product destination |
Asynchronous motors
|
|
product specific application |
Pumps and fans in HVAC
|
|
assembly style |
With heat sink
|
|
network number of phases |
3 phases
|
|
motor power kW |
75 kW
|
|
motor power hp |
100 hp
|
|
[Us] rated supply voltage |
380…480 V – 15…10 %
|
|
supply voltage limits |
323…528 V
|
|
supply frequency |
50…60 Hz – 5…5 %
|
|
EMC filter |
Class C2 EMC filter integrated
|
|
line current |
141.8 A at 380 V
111.3 A at 480 V |
apparent power |
105.3 kVA at 380 V
|
|
---|---|---|
prospective line Isc |
22 kA
|
|
continuous output current |
160 A at 380 V
160 A at 460 V |
|
maximum transient current |
176 A for 60 s
|
|
speed drive output frequency |
0.5…200 Hz
|
|
nominal switching frequency |
8 kHz
|
|
switching frequency |
6…16 kHz adjustable
8…16 kHz with derating factor |
|
speed range |
1…10
|
|
speed accuracy |
+/- 10 % of nominal slip 0.2 Tn to Tn
|
|
torque accuracy |
+/- 15 %
|
|
transient overtorque |
120 % of nominal motor torque +/- 10 % for 60 s
|
|
asynchronous motor control profile |
Voltage/frequency ratio – Energy Saving, quadratic U/f
Flux vector control without sensor, standard Voltage/frequency ratio, 5 points Voltage/frequency ratio, 2 points Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo) |
|
regulation loop |
Adjustable PI regulator
|
|
motor slip compensation |
Adjustable
Not available in voltage/frequency ratio motor control Automatic whatever the load |
|
local signalling |
1 LED (red) for DC bus energized
|
|
output voltage |
<= power supply voltage
|
|
isolation |
Electrical between power and control
|
|
type of cable |
Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR
Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC With UL Type 1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC |
|
electrical connection |
VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES: terminal 2.5 mm² / AWG 14
L1/R, L2/S, L3/T: terminal 150 mm² (300 kcmil) |
|
tightening torque |
0.6 N.m (VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES)
41 N.m, 360 lb.in (L1/R, L2/S, L3/T) |
|
supply |
Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 A, protection type: overload and short-circuit protection
Internal supply: 24 V DC (21…27 V), <200 A, protection type: overload and short-circuit protection |
|
analogue input number |
2
|
|
analogue input type |
VIA switch-configurable voltage: 0…10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits
VIB configurable voltage: 0…10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits VIB configurable PTC probe: 0…6 probes, impedance: 1500 Ohm VIA switch-configurable current: 0…20 mA, impedance: 250 Ohm, resolution 10 bits |
|
sampling duration |
2 ms +/- 0.5 ms F discrete
2 ms +/- 0.5 ms R discrete 2 ms +/- 0.5 ms RES discrete 3.5 ms +/- 0.5 ms VIA analog 22 ms +/- 0.5 ms VIB analog |
|
response time |
FM 2 ms, tolerance +/- 0.5 ms for analog output(s)
FLA, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s) FLB, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s) RY, RC 7 ms, tolerance +/- 0.5 ms for discrete output(s) |
|
accuracy |
+/- 0.6 % (VIA) for a temperature variation 60 °C
+/- 0.6 % (VIB) for a temperature variation 60 °C +/- 1 % (FM) for a temperature variation 60 °C |
|
linearity error |
VIA: +/- 0.15 % of maximum value for input
VIB: +/- 0.15 % of maximum value for input FM: +/- 0.2 % for output |
|
analogue output number |
1
|
|
analogue output type |
FM switch-configurable voltage 0…10 V DC, impedance: 7620 Ohm, resolution 10 bits
FM switch-configurable current 0…20 mA, impedance: 970 Ohm, resolution 10 bits |
|
discrete output number |
2
|
|
discrete output type |
Configurable relay logic: (FLA, FLC) NO – 100000 cycles
Configurable relay logic: (FLB, FLC) NC – 100000 cycles Configurable relay logic: (RY, RC) NO – 100000 cycles |
|
minimum switching current |
3 mA at 24 V DC for configurable relay logic
|
|
maximum switching current |
5 A at 250 V AC on resistive load – cos phi = 1 – L/R = 0 ms (FL, R)
5 A at 30 V DC on resistive load – cos phi = 1 – L/R = 0 ms (FL, R) 2 A at 250 V AC on inductive load – cos phi = 0.4 – L/R = 7 ms (FL, R) 2 A at 30 V DC on inductive load – cos phi = 0.4 – L/R = 7 ms (FL, R) |
|
discrete input type |
F programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
R programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm RES programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm |
|
discrete input logic |
Positive logic (source) (F, R, RES), <= 5 V (state 0), >= 11 V (state 1)
Negative logic (sink) (F, R, RES), >= 16 V (state 0), <= 10 V (state 1) |
|
acceleration and deceleration ramps |
Linear adjustable separately from 0.01 to 3200 s
Automatic based on the load |
|
braking to standstill |
By DC injection
|
|
protection type |
Overheating protection: drive
Thermal power stage: drive Short-circuit between motor phases: drive Input phase breaks: drive Overcurrent between output phases and earth: drive Overvoltages on the DC bus: drive Break on the control circuit: drive Against exceeding limit speed: drive Line supply overvoltage and undervoltage: drive Line supply undervoltage: drive Against input phase loss: drive Thermal protection: motor Motor phase break: motor With PTC probes: motor |
|
dielectric strength |
3535 V DC between earth and power terminals
5092 V DC between control and power terminals |
|
insulation resistance |
>= 1 mOhm 500 V DC for 1 minute
|
|
frequency resolution |
Display unit: 0.1 Hz
Analog input: 0.024/50 Hz |
|
communication port protocol |
BACnet
METASYS N2 Modbus LonWorks APOGEE FLN |
|
connector type |
1 RJ45
1 open style |
|
physical interface |
2-wire RS 485
|
|
transmission frame |
RTU
|
|
transmission rate |
9600 bps or 19200 bps
|
|
data format |
8 bits, 1 stop, odd even or no configurable parity
|
|
type of polarization |
No impedance
|
|
number of addresses |
1…247
|
|
communication service |
Write single register (06)
Time out setting from 0.1 to 100 s Read device identification (43) Write multiple registers (16) 2 words maximum Monitoring inhibitable Read holding registers (03) 2 words maximum |
|
option card |
Communication card for LonWorks
|
|
operating position |
Vertical +/- 10 degree
|
|
width |
362 mm
|
|
height |
1000 mm
|
|
depth |
364 mm
|
|
functionality |
Mid
|
|
specific application |
HVAC
|
|
IP degree of protection |
IP55
|
Reviews