C10N3TM016 – ComPacT NSX100N Circuit Breaker, 16A, 3P Fixed, 50kA at 415VAC
The Schneider Electric ComPacT NSX100N (C10N3TM016) is a compact, high-performance 3-pole fixed circuit breaker designed for reliable distribution protection.
Rated at 16A with a thermal-magnetic (TMD) trip unit, it ensures overload (thermal) and short-circuit (magnetic) protection in compliance with IEC 60947-2.
With a breaking capacity of 50kA at 415VAC, this breaker is ideal for both standard and demanding low-voltage applications. Its space-saving design (105 × 161 × 86 mm) makes it suitable for modern electrical panels, and it supports a wide range of accessories and auxiliaries for flexible operation.
Key Features
-
Range: ComPacT NSX (new generation)
-
Product type: Circuit Breaker
-
Application: Distribution
-
Poles: 3P (3D protected)
-
Rated Current (In): 16A at 40°C
-
Operational Voltage (Ue): 690VAC, 50/60Hz
-
Insulation Voltage (Ui): 800VAC
-
Impulse Withstand Voltage (Uimp): 8kV
-
Control: Toggle (manual ON/OFF + push-to-trip)
-
Mounting Mode: Fixed, backplate mounting
-
Suitability for Isolation: Yes (IEC 60947-2)
Breaking Capacity (Icu – IEC 60947-2)
-
90kA at 220/240VAC
-
50kA at 380/415VAC
-
50kA at 440VAC
-
36kA at 500VAC
-
35kA at 525VAC
-
10kA at 660/690VAC
Service Breaking Capacity (Ics): Same as Icu values.
Trip Unit – TMD (Thermal-Magnetic)
-
Technology: Thermal-Magnetic
-
Functions: LI (Long-time overload, Instantaneous short-circuit)
-
Rated Current: 16A
-
Adjustments:
-
Long-time pickup (Ir): 0.7…1 × In
-
Long-time delay (tr): Fixed – 120–400s at 1.5 × In; 15s at 6 × Ir
-
Instantaneous pickup (Ii): Fixed at 190A
-
Durability & Performance
-
Mechanical Endurance: 50,000 cycles
-
Electrical Endurance:
-
30,000 cycles at 440V In
-
20,000 cycles at 690V In/2
-
10,000 cycles at 690V In
-
-
Power Losses: 2.92W per pole
Dimensions & Weight
-
Width: 105 mm
-
Height: 161 mm
-
Depth: 86 mm
-
Weight: 2.05 kg
Connections & Mounting
-
Upside/Downside Connection: Front terminals
-
Pitch: 35 mm
-
Mounting: Backplate, flat on back, horizontal or vertical position
-
Number of Slots: 5
Environmental Ratings
-
Operating Temperature: -25°C to +70°C
-
Storage Temperature: -50°C to +85°C
-
Relative Humidity: 0–95%
-
Altitude:
-
0–2000m without derating
-
2000–5000m with derating
-
-
Degree of Protection:
-
IP40 (front face)
-
IK07 impact resistance
-
Class II electrical shock protection
-
-
Pollution Degree: 3 (IEC 60664-1)
-
Standards & Certifications: IEC 60947-2, CCC, EAC, Marine approved
✅ Applications:
The ComPacT NSX100N (C10N3TM016) is designed for industrial, commercial, and infrastructure distribution systems, offering compact size, high breaking capacity, and flexible protection with thermal-magnetic trip technology.