Sale!

CAD50BD TeSys D control relay – 5 NO – <= 690 V - 24 V DC standard coil

27,142.00 7.5% VAT

TeSys D control relay – 5 NO – <= 690 V – 24 V DC standard coil

 

SKU: CAD50BD Category:
Main
range
TeSys
product name
TeSys CAD
product or component type
Control relay
device short name
CAD
contactor application
Control circuit
Complementary
utilisation category
AC-14
DC-13
AC-15
pole contact composition
5 NO
[Ue] rated operational voltage
<= 690 V AC 25…400 Hz
control circuit type
DC standard
[Uc] control circuit voltage
24 V DC
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947
[Ith] conventional free air thermal current
10 A (at 60 °C)
Irms rated making capacity
140 A AC conforming to IEC 60947-5-1
250 A DC conforming to IEC 60947-5-1
[Icw] rated short-time withstand current
100 A – 1 s
120 A – 500 ms
140 A – 100 ms
associated fuse rating
10 A gG conforming to IEC 60947-5-1
[Ui] rated insulation voltage
600 V UL certified
600 V CSA certified
690 V conforming to IEC 60947-5-1
mounting support
Rail
Plate
connections – terminals
Screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
tightening torque
1.2 N.m – on screw clamp terminals – with screwdriver Philips No 2
1.2 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm
control circuit voltage limits
0.1…0.25 Uc (-40…70 °C):drop-out DC
0.7…1.25 Uc (-40…60 °C):operational DC
1…1.25 Uc (60…70 °C):operational DC
operating time
53…72 ms coil energisation and NO closing
16…24 ms coil de-energisation and NO opening
mechanical durability
30 Mcycles
maximum operating rate
180 cyc/mn
time constant
28 ms
inrush power in W
5.4 W (at 20 °C)
hold-in power consumption in W
5.4 W at 20 °C
minimum switching voltage
17 V
minimum switching current
5 mA
non-overlap time
1.5 ms on energisation between NC and NO contact
1.5 ms on de-energisation between NC and NO contact
insulation resistance
> 10 MOhm
mechanical robustness
Shocks control relay open: 10 Gn for 11 ms conforming to IEC 60068-2-27
Shocks control relay closed: 15 Gn for 11 ms conforming to IEC 60068-2-27
Vibrations control relay open: 2 Gn, 5…300 Hz conforming to IEC 60068-2-6
Vibrations control relay closed: 4 Gn, 5…300 Hz conforming to IEC 60068-2-6
height
77 mm
width
45 mm
depth
93 mm
net weight
0.58 kg

Reviews

There are no reviews yet.

Only logged in customers who have purchased this product may leave a review.