range of product |
Harmony XB5
|
|
---|---|---|
product or component type |
Emergency switching off push-button
|
|
device short name |
XB5
|
|
bezel material |
Dark grey plastic
|
|
fixing collar material |
Plastic
|
|
head type |
Standard
|
|
mounting diameter |
22 mm
|
|
sale per indivisible quantity |
1
|
|
shape of signaling unit head |
Round
|
|
type of operator |
trigger action and mechanical latching
|
|
reset |
Turn to release
|
|
operator profile |
Red mushroom Ø 40 mm, unmarked
|
|
contacts type and composition |
2 NC
|
|
contact operation |
Slow-break
|
|
connections – terminals |
Screw clamp terminals, <= 2 x 1.5 mm² with cable end conforming to EN 60947-1
Screw clamp terminals, >= 1 x 0.22 mm² without cable end conforming to EN 60947-1 |
|
device presentation |
Complete product
|
height |
43 mm
|
|
---|---|---|
width |
40 mm
|
|
depth |
82 mm
|
|
terminals description ISO n°1 |
(11-12)NC
|
|
net weight |
0.072 kg
|
|
resistance to high pressure washer |
7000000 Pa at 55 °C, distance : 0.1 m
|
|
contacts usage |
Standard contacts
|
|
positive opening |
With conforming to EN/IEC 60947-5-1 appendix K
|
|
operating travel |
1.5 mm (NC changing electrical state)
4.3 mm (total travel) |
|
mechanical durability |
300000 cycles
|
|
tightening torque |
0.8…1.2 N.m conforming to EN 60947-1
|
|
shape of screw head |
Cross compatible with Philips no 1 screwdriver
Cross compatible with pozidriv No 1 screwdriver Slotted compatible with flat Ø 4 mm screwdriver Slotted compatible with flat Ø 5.5 mm screwdriver |
|
contacts material |
Silver alloy (Ag/Ni)
|
|
short-circuit protection |
10 A cartridge fuse type gG conforming to EN/IEC 60947-5-1
|
|
[Ith] conventional free air thermal current |
10 A conforming to EN/IEC 60947-5-1
|
|
[Ui] rated insulation voltage |
600 V (pollution degree 3) conforming to EN 60947-1
|
|
[Uimp] rated impulse withstand voltage |
EN 60947-1 6 kV
|
|
[Ie] rated operational current |
3 A at 240 V, AC-15, A600 conforming to EN/IEC 60947-5-1
6 A at 120 V, AC-15, A600 conforming to EN/IEC 60947-5-1 0.1 A at 600 V, DC-13, Q600 conforming to EN/IEC 60947-5-1 0.27 A at 250 V, DC-13, Q600 conforming to EN/IEC 60947-5-1 0.55 A at 125 V, DC-13, Q600 conforming to EN/IEC 60947-5-1 1.2 A at 600 V, AC-15, A600 conforming to EN/IEC 60947-5-1 |
|
electrical durability |
1000000 cycles, AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, AC-15, 3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C 1000000 cycles, AC-15, 4 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C 1000000 cycles, DC-13, 0.2 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C 1000000 cycles, DC-13, 0.5 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C |
|
electrical reliability |
Λ < 10exp(-6) at 5 V, 1 mA in clean environment conforming to EN/IEC 60947-5-4
Λ < 10exp(-8) at 17 V, 5 mA in clean environment conforming to EN/IEC 60947-5-4 |