Sale!

GV2P20 Motor circuit breaker, TeSys GV2, 3P, 13-18 A, thermal magnetic, screw clamp terminals

38,861.00 7.5% VAT

Motor circuit breaker, TeSys GV2, 3P, 13-18 A, thermal magnetic, screw clamp terminals

 

Available on back-order

Main
range
TeSys
product name
TeSys GV2
device short name
GV2P
device application
Motor
trip unit technology
Thermal-magnetic
Complementary
poles description
3P
network type
AC
utilisation category
AC-3 conforming to IEC 60947-4-1
Category A conforming to IEC 60947-2
network frequency
50/60 Hz conforming to IEC 60947-4-1
fixing mode
35 mm symmetrical DIN rail: clipped
Panel: screwed (with 2 x M4 screws)
operating position
Any position
motor power kW
7.5 kW at 400/415 V AC 50/60 Hz
9 kW at 500 V AC 50/60 Hz
15 kW at 690 V AC 50/60 Hz
breaking capacity
100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
4 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity
100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
50 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
75 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
control type
Rotary knob
[In] rated current
18 A
thermal protection adjustment range
13…18 A
magnetic tripping current
223 A
[Ue] rated operational voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
[Ith] conventional free air thermal current
18 A conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage
6 kV IEC 60947-2
power dissipation per pole
2.5 W
mechanical durability
100000 cycles
electrical durability
100000 cycles for AC-3 at 440 V
maximum operating rate
25 cyc/h
rated duty
Continuous conforming to IEC 60947-4-1
tightening torque
1.7 N.m on screw clamp terminals
suitability for isolation
Yes conforming to IEC 60947-1
phase failure sensitivity
Yes conforming to IEC 60947-4-1
height
89 mm
width
45 mm
depth
97 mm

Reviews

There are no reviews yet.

Only logged in customers who have purchased this product may leave a review.