range |
ComPact
|
|
---|---|---|
product name |
ComPact NSX
|
|
range of product |
ComPact NSX100…250
|
|
device short name |
NSX100F
|
|
product or component type |
Circuit breaker
|
|
device application |
Distribution
|
|
Number of poles |
4P
|
|
protected poles description |
3t
|
|
neutral position |
Left
|
|
[In] rated current |
80 A at 40 °C
|
|
[Ue] rated operational voltage |
690 V AC 50/60 Hz
|
|
network type |
AC
|
|
network frequency |
50/60 Hz
|
|
suitability for isolation |
Yes conforming to EN/IEC 60947-2
|
|
utilisation category |
Category A
|
|
[Icu] rated ultimate short-circuit breaking capacity |
10 kA at 600 V AC 50/60 Hz conforming to UL 508
25 kA at 480 V AC 50/60 Hz conforming to UL 508 85 kA at 240 V AC 50/60 Hz conforming to UL 508 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
|
Performance level |
F 36 kA 415 V AC
|
|
trip unit name |
TM-D
|
|
trip unit technology |
Thermal-magnetic
|
|
trip unit protection functions |
LI
|
|
control type |
Toggle
|
|
Circuit breaker mounting mode |
Fixed
|
[Ui] rated insulation voltage |
800 V AC 50/60 Hz
|
|
---|---|---|
[Uimp] rated impulse withstand voltage |
8 kV
|
|
[Ics] rated service short-circuit breaking capacity |
11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 |
|
mechanical durability |
50000 cycles
|
|
electrical durability |
10000 cycles at 690 V In
20000 cycles at 690 V In/2 30000 cycles at 440 V In 50000 cycles at 440 V In/2 |
|
mounting support |
Backplate
|
|
upside connection |
Front
|
|
downside connection |
Front
|
|
connection pitch |
35 mm
|
|
protection type |
L : for overload protection (thermal)
I : for short-circuit protection (magnetic) |
|
trip unit rating |
80 A at 40 °C
|
|
Long-time pick-up adjustment type Ir (thermal protection) |
Adjustable
|
|
[Ir] long-time protection pick-up adjustment range |
0.7…1 x In
|
|
Long-time protection delay adjustment type tr |
Fixed
|
|
[tr] long-time protection delay adjustment range |
120…400 s at 1.5 x In
15 s at 6 x Ir |
|
Short-time protection pick-up adjustment type Isd |
Fixed
|
|
[Isd] Short-time protection pick-up adjustment range |
640 A
|
|
Short-time protection delay adjustment type tsd |
Fixed
|
|
earth-leakage protection |
Without
|
|
Neutral protection settings |
No protection (3t)
|
|
Number of slots for electrical auxiliaries |
5 slot(s)
|
|
Width (W) |
140 mm
|
|
Height (H) |
161 mm
|
|
Depth (D) |
86 mm
|
|
net weight |
2.4 kg
|