| range of product |
Easypact CVS100…250
|
|
|---|---|---|
| product or component type |
Circuit breaker
|
|
| device short name |
CVS160F
|
|
| device application |
Distribution
|
|
| poles description |
3P
|
|
| protected poles description |
3d
|
|
| Earth leakage protection (Vigi add on) |
Without
|
|
| [In] rated current |
160 A at 40 °C
|
|
| breaking capacity code |
F
|
|
| network type |
AC
|
|
| [Icu] Breaking capacity |
36 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
|
| utilisation category |
Category A
|
|
| trip unit name |
TM-D
|
|
| trip unit technology |
Thermal-magnetic
|
|
| trip unit rating |
160 A at 40 °C
|
|
| protection type |
Short-circuit protection (magnetic)
Overload protection (thermal) |
| network frequency |
50/60 Hz
|
|
|---|---|---|
| control type |
Toggle
|
|
| mounting mode |
Fixed
|
|
| mounting support |
Backplate
|
|
| upside connection |
Front
|
|
| downside connection |
Front
|
|
| connections – terminals |
Screw connection
|
|
| [Uimp] rated impulse withstand voltage |
8 kV conforming to EN/IEC 60947-2
|
|
| thermal protection adjustment range |
112…160 A
|
|
| [Ics] rated service breaking capacity |
18 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
|
| mechanical durability |
25000 cycles
|
|
| electrical durability |
12000 cycles 415 V In conforming to IEC 60947-2
|
|
| connection pitch |
35 mm
|
|
| contact position indicator |
Yes
|
|
| long time pick-up adjustment type Ir |
Adjustable
|
|
| long time pick-up adjustment range |
0.7…1 x In
|
|
| long time delay adjustment type |
Fixed
|
|
| instantaneous pick-up adjustment type Ii |
Fixed
|
|
| instantaneous pick-up adjustment range |
1250 A
|
|
| height |
161 mm
|
|
| width |
105 mm
|
|
| depth |
86 mm
|
|
| net weight |
1.8 kg
|





Reviews
There are no reviews yet