range |
EasyLogic
|
|
---|---|---|
product name |
EasyLogic PM2100
|
|
device short name |
PM2110
|
|
product or component type |
Power meter
|
device application |
Power monitoring
Sub billing |
|
---|---|---|
power quality analysis |
total harmonic distortion
|
|
type of measurement |
Total current harmonic distortion THD (I) per phase
Total voltage harmonic distortion THD (U) per phase Apparent energy total Active and reactive energy total Apparent power total Active and reactive power total Current average Voltage average Frequency average Power factor average |
|
metering type |
Peak demand power PM, QM, SM
Apparent power S, S1, S2, S3 Current I, I1, I2, I3 Reactive power Q, Q1, Q2, Q3 Calculated neutral current Voltage U, U21, U32, U13, V, V1, V2, V3 Peak demand currents Unbalance current Demand power P, Q, S Active power P, P1, P2, P3 Active, reactive, apparent energy (signed, four quadrant) |
|
accuracy class |
Class 1 active energy conforming to IEC 62053-21
Class 1 reactive energy conforming to IEC 62053-24 |
|
measurement accuracy |
Apparent power +/- 1 %
Active energy +/- 1 % Reactive energy +/- 1 % Active power +/- 1 % Voltage +/- 0.5 % Power factor +/- 0.01 Current +/- 0.5 % Frequency +/- 0.05 % |
|
measurement current |
5…6000 mA
|
|
measurement voltage |
35…480 V AC 50/60 Hz between phases
20…277 V AC 50/60 Hz between phase and neutral 480…999000 V AC 50/60 Hz with external VT |
|
frequency measurement range |
45…65 Hz
|
|
[Us] rated supply voltage |
44…277 V AC 45…65 Hz +/- 10 %
44…277 V DC +/- 10 % |
|
network frequency |
60 Hz
50 Hz |
|
ride-through time |
100 ms 120 V AC typical
400 ms 230 V AC typical 50 ms 125 V DC typical |
|
[In] rated current |
5 A
1 A |
|
maximum power consumption in VA |
6 VA at 277 V AC
|
|
maximum power consumption in W |
3.3 W (power lines (AC))
2 W at 277 V (power lines (DC)) |
|
input impedance |
Current (impedance <= 0.3 mOhm)
Voltage (impedance > 5 MOhm) |
|
tamperproof of settings |
Protected by access code
|
|
display type |
7 segments LED
|
|
display colour |
Red
|
|
messages display capacity |
3 fields of 4 characters
|
|
display digits |
12 digit(s) – 14.2 mm in height
|
|
Demand intervals |
Configurable from 1 to 60 min
|
|
information displayed |
Demand current (past value)
Demand current (present value) Demand power (past value) Demand power (present value) Voltage Current Frequency Energy consumption Harmonic distortion Power factor Active power Apparent power Reactive power Unbalanced in % |
|
control type |
3 x button
|
|
local signalling |
Red LED: output signal 1…9999000 pulse/ k_h (kWh, kVAh, kVARh)
Green LED: module operating (RUN) |
|
number of inputs |
0
|
|
number of outputs |
1 pulse
|
|
POP parameter |
Pulse: 20 ms (5…40 V DC, 20 mA max)1…9999000 pulse/ k_h (kWh, kVAh, kVARh)
|
|
impulse duration |
20 ms
|
|
communication port protocol |
POP
|
|
sampling rate |
64 samples/cycle
|
|
cybersecurity |
Enable/disable communication ports
|
|
communication service |
Remote monitoring
|
|
product certifications |
CE conforming to IEC 61010-1
CULus conforming to UL 61010-1 CULus conforming to CSA C22.2 No 61010-1 RCM EAC C-Tick |
|
mounting mode |
Clip-on
|
|
mounting position |
Vertical
|
|
mounting support |
Framework
|
|
provided equipment |
1 x installation guide
|
|
measurement category |
Category III 480 V
Category II 480…600 V |
|
electrical insulation class |
Double insulation
Class II |
|
flame retardance |
V-0 conforming to UL 94
|
|
connections – terminals |
Current transformer: screw connection (bottom) 6
Voltage inputs: screw connection (top) 4 |
|
material |
Polycarbonate
|
|
width |
96 mm
|
|
depth |
76.09 mm total:
61.64 mm embedded: |
|
height |
96 mm
|
|
net weight |
300 g
|
|
compatibility code |
PM2110
|