Sale!

MVS40N3MW2A EP MVS CB 4000A 55kA 3P MDO ETA2 drawout manual Circuit breaker

4,314,172.00 7.5% VAT

EP MVS CB 4000A 55kA 3P MDO ETA2 drawout manual Circuit breaker

 

Main
range of product
EasyPact MVS
range
EasyPact
product name
MVS40N
device short name
MVS40N
product or component type
Circuit breaker
device application
Distribution
poles description
3P
protected poles description
3P 3d
network type
AC
breaking capacity code
N
suitability for isolation
Yes conforming to IEC 60947-2
utilisation category
Category B
trip unit name
ETA2I
trip unit technology
Electronic
trip unit rating
4000 A
Complementary
network frequency
50/60 Hz
control type
Manually operated
mounting mode
Drawout
mounting support
Rail
Base plate
connection position
Horizontal
Vertical
location of connection
Rear
[In] rated current
4000 A at 40 °C
[Ui] rated insulation voltage
1000 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage
12 kV conforming to IEC 60947-2
[Ue] rated operational voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
circuit breaker CT rating
4000 A
breaking capacity
55 kA Icu at 220…440 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity
55 kA (Ics) at 220…440 V AC 50/60 Hz conforming to IEC 60947-2
mechanical durability
20000 cycles (with maintenance) conforming to IEC 60947-2
10000 cycles (without maintenance) conforming to IEC 60947-2
electrical durability
Category B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Category B: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
connection pitch
115 mm without spreader
contact position indicator
Yes
[Icm] rated short-circuit making capacity
121 kA (Icm) at 220…440 V AC 50/60 Hz conforming to IEC 60947-2
[Icw] rated short-time withstand current
42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2
55 kA (1 s) at 220…440 V AC 50/60 Hz conforming to IEC 60947-2
30 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
trip unit protection functions
LI
protection type
Instantaneous short-circuit protection
Overload protection (long time)
fault indication
Overload
Internal fault
Short-circuit
long time pick-up adjustment type Ir
Adjustable 9 settings
long time pick-up adjustment range
0.4…1 x In
long time delay adjustment type
Adjustable 9 settings
[tr] long-time delay adjustment range
0.5…24 s at 6 x Ir
thermal memory
20 minutes before and after tripping
instantaneous pick-up adjustment type Ii
Adjustable 9 settings
instantaneous pick-up adjustment range
1.5…10 x Ir
zone selective interlocking ZSI
With
display type
Digital display
type of measurement
Current
current sensor rating range
1000/4000 A
maximum breaking time
25 ms
maximum closing response time
70 ms
height
439 mm
width
441 mm
depth
395 mm
net weight
90 kg

Reviews

There are no reviews yet.

Only logged in customers who have purchased this product may leave a review.