| range of product |
Harmony Relay
|
|
|---|---|---|
| series name |
Miniature
|
|
| product or component type |
Plug-in relay
|
|
| device short name |
RXM
|
|
| contacts type and composition |
2 C/O
|
|
| [Uc] control circuit voltage |
48 V DC
|
|
| [Ithe] conventional enclosed thermal current |
12 A at -40…55 °C
|
|
| status LED |
Without
|
|
| control type |
Lockable test button
|
|
| utilisation coefficient |
20 %
|
| shape of pin |
Flat
|
|
|---|---|---|
| [Ui] rated insulation voltage |
250 V conforming to IEC
300 V conforming to CSA 300 V conforming to UL |
|
| [Uimp] rated impulse withstand voltage |
4 kV during 1.2/50 µs
|
|
| contacts material |
AgNi
|
|
| [Ie] rated operational current |
12 A at 28 V (DC) NO conforming to IEC
12 A at 250 V (AC) NO conforming to IEC 6 A at 28 V (DC) NC conforming to IEC 6 A at 250 V (AC) NC conforming to IEC 12 A at 28 V (DC) conforming to UL 12 A at 277 V (AC) conforming to UL |
|
| maximum switching voltage |
250 V conforming to IEC
|
|
| resistive rated load |
12 A at 250 V AC
12 A at 28 V DC |
|
| maximum switching capacity |
3000 VA/336 W
|
|
| minimum switching capacity |
170 mW at 10 mA, 17 V
|
|
| operating rate |
<= 1200 cycles/hour under load
<= 18000 cycles/hour no-load |
|
| mechanical durability |
10000000 cycles
|
|
| electrical durability |
100000 cycles for resistive load
|
|
| average coil consumption in W |
0.9 W
|
|
| drop-out voltage threshold |
>= 0.1 Uc
|
|
| operate time |
20 ms
|
|
| release time |
20 ms
|
|
| average coil resistance |
2560 Ohm at 20 °C +/- 10 %
|
|
| rated operational voltage limits |
38.4…52.8 V DC
|
|
| safety reliability data |
B10d = 100000
|
|
| protection category |
RT I
|
|
| test levels |
Level A group mounting
|
|
| operating position |
Any position
|
|
| net weight |
0.037 kg
|
|
| device presentation |
Complete product
|





Reviews