| network rated voltage |
400 V AC 50 Hz
415 V AC 50 Hz |
|
|---|---|---|
| reactive power rating |
150 kvar
|
|
| operating mode |
Fixed
|
|
| range |
VarSet
|
|
| device short name |
VarSet fixed
|
|
| product or component type |
Capacitor bank
|
| network pollution level |
Low polluted
|
|
|---|---|---|
| [Gh/Sn] harmonic pollution rate |
15…25 %
|
|
| [THDU] total harmonic distorsion of voltage |
3…4 %
|
|
| power per step |
150 kvar
|
|
| step composition |
150
|
|
| location of connection |
Bottom
|
|
| capacitor technology |
VarplusCan
|
|
| poles description |
3P
|
|
| capacitance tolerance |
– 5 % to 10 %
|
|
| [Ui] rated insulation voltage |
690 V
|
|
| [Uimp] rated impulse withstand voltage |
8 kV
|
|
| maximum permissible voltage |
1.1 x Un (8 hours over 24 hours) conforming to IEC 60831
|
|
| [Imp] maximum permanent current |
Capacitor: 1.8 x In at 480 V conforming to IEC 60831
Battery: 1.43 x In at 400 V conforming to IEC 61439-2 Battery: 1.19 x In at 415 V conforming to IEC 61439-2 |
|
| main incomer protection |
Circuit breaker protection
|
|
| breaking capacity |
Icu 50 kA
|
|
| control type |
Rotary handle
|
|
| accessibility for operation |
Front
|
|
| colour |
Grey (RAL 7035)
|
|
| maximum weight |
131 kg
|
|
| height |
1300 mm
|
|
| width |
800 mm
|
|
| depth |
300 mm
|
|
| provided equipment |
Auxiliary transformer
|
|
| internal voltage transformer |
400/230 V – 250 VA
|
|
| function available |
Alarm contact
GenSet shedding contact |






Reviews